Inspections for the day of: Friday, October 21, 2005.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00559 INSP-Final Inspection10/19/200510/21/200510/21/2005 5:29:48 PMPCANC
No time available for this inspection today, spoke with Kelly to reschedule for monday 10/24 per our agreement.
FIR05-00492 INSP-Final Inspection10/20/200510/21/200510/21/2005 5:28:33 PMPCANC
No time for this inspection today, spoke with Rick to reschedule for monday 10/24.
FIR05-00426 INSP-Alarm Testing10/21/200510/21/200510/21/2005 5:27:19 PMPFAIL
Provide correct sample tubes for the duct width intended, verify correct location for duct detectors, strobe in seating area is overspaced and installed on the wrong column, one 75cd strobe in the kitchen area is blocked, the strobes for outside seating area do not match approved plan, no other items tested at this time.
FIR05-00089 INSP-Sprinkler Rough-in/Hydro10/21/200510/21/200510/21/2005 5:21:31 PMPNR
Cancel inspection per conversation with Brian.
FIR05-00076 INSP-Alarm Testing10/21/200510/21/200510/21/2005 5:20:10 PMPFAIL
Lower pull station to 48" AFF, provide additional smoke at the panel due to beam blockage, verify audibility in the FACP room, fire pump run shows as an alarm and the matrix indicates a supervisory, change label at roof tamper and stair flow 108, outside bell shall silence upon waterflow ceasation, all sprinkler alarms tested today, no other items tested at this time.
MIS05-00079 FIR-Final10/20/200510/21/200510/21/2005 5:13:05 PMAFAIL
Overhead roll up door is not allowed above the main entry/exit to block the egress under any circumstance in this A3 occupancy.
FIR05-00075 INSP-Alarm Testing10/18/200510/21/200510/21/2005 5:10:46 PMAFAIL
Heat detector in the north elevator pit is too far from the sprinkler head, provide resubmittals for the EOL 2nd floor, tape on strobe and no ceiling tile 1st floor north, west elevator is not complete, provide sign at the door to FACP room, provide audible notification for the electrical room and FACP, provide knox box.
FIR05-00459 INSP-Alarm Testing10/20/200510/21/200510/21/2005 5:04:04 PMANR
The core and shell permit must be finaled prior to TI approval.
FIR05-00406 INSP-Final Inspection10/20/200510/21/200510/21/2005 4:55:31 PMAPART
Area notification devices tested satisfactory except in two areas which are not complete yet, will final when all devices have been installed and EOL is measured.
FIR05-00089 INSP-Final Inspection10/19/200510/21/200510/20/2005 8:44:23 AMACANC
contact brian calkins.; Phone #: ###-#### Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley