Inspections for the day of: Friday, October 21, 2005.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01223 BLD-Aging Inspection10/21/200510/21/200510/27/2005 2:52:25 PM NR
I left a message for Scott to get this finaled.
FIR01-00624 FIR-Aging Inspection10/21/200510/21/200510/23/2005 8:45:13 PM PASS
FIR02-00388 FIR-Aging Inspection10/21/200510/21/200510/23/2005 8:43:15 PM DONE
Greg Patrick will follow up
FIR01-00625 FIR-Aging Inspection10/21/200510/21/200510/23/2005 8:42:28 PM PASS
BLD05-01484 FIRE-Conference10/20/200510/21/200510/23/2005 8:39:19 PMPNR
Fire alarm permit needs finaled. Per Ralph with Alarmco the work will be done next week and the inspection called in.
FIR05-00598 INSP-Conference10/21/200510/21/200510/23/2005 8:38:24 PMPNR
Ralph; ###-#### Work is to be completed next week and inspection called in.
FIR05-00660 INSP-Sprinkler Rough-in10/21/200510/21/200510/23/2005 8:37:33 PMPPASS
PIV valve installed. Stem still needs installed.
BLD05-00235 FIRE-Final Inspection10/21/200510/21/200510/21/2005 11:52:31 AMPPART
A temporary occupancy was given with Dave's permission until the curbing has been corrected for fire dept access
FIR05-00190 INSP-Sprinkler Rough-in/Hydro10/20/200510/21/200510/21/2005 11:26:57 AMAFAIL
The sprinkler piping doesn't match installation for the Special Services area. Contractor needs to resubmit plans that match installation. A 1 1/2" loop has been installed and 1 1/4" branchline is being used to supply new pendants that is not shown on the plans.
MIS05-00190 FIR-Final10/20/200510/21/200510/21/2005 10:24:16 AMAPART
A temp was given. Items needing correction include overspaced sprinklers, missing canopy on the restroom sprinkler, repair or remove the exit sign, mount the fire extinguisher, remove thumbturns from both exit doors and provide with approved hardware or make egress side keyed and provide indicators as discussed.
BLD05-00235 FIRE-Final Inspection10/20/200510/21/200510/21/2005 10:09:51 AMAFAIL
Fire dept access is not per revised/approved plans for access through the east entrance.
BLD05-02744 FIRE-Final Inspection10/21/200510/21/200510/21/2005 9:27:43 AMAPASS
fire life safety finaled
BLD05-00496 FIRE-Final Inspection10/20/200510/21/200510/21/2005 8:32:39 AMAPASS
fire life safety finaled
FIR01-00625 INSP-Final Inspection10/21/200510/21/200510/21/2005 12:00:00 AMPPASS
permit finaled
FIR05-00658 INSP-Final Inspection10/19/200510/21/200510/20/2005 2:44:48 PMAPASS
Permit finaled