Inspections for the day of: Tuesday, October 21, 2008.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-02493 Rough-In Permanent Service10/21/200810/21/200810/21/2008 4:14:32 PMPPASS
eric Phone #: ###-#### p/s u/g n ok, esc response only once
ELE08-01901 Rough-In Permanent Service10/21/200810/21/200810/21/2008 3:44:36 PMPPASS
eric Phone #: ###-#### p/s u/g n ok, one response only to esc
ELE07-02473 ELE-Aging Inspection10/21/200810/21/200810/21/2008 3:28:32 PM DONE
still working on job, no lighting installed
ESC08-00155 General Inspection10/21/200810/21/200810/21/2008 3:15:02 PMPPASS
looked ok
ESC08-00152 General Inspection10/21/200810/21/200810/21/2008 3:13:42 PMPPASS
looked ok
ESC08-00741 General Inspection10/21/200810/21/200810/21/2008 3:12:47 PMAPASS
looked ok
ESC08-00504 General Inspection10/21/200810/21/200810/21/2008 3:11:20 PMAPASS
looked ok
ELE08-02559 Permanent Service10/20/200810/21/200810/21/2008 2:18:52 PMPPASS
Contact Mark Kinch for any questions. Phone #: ###-#### Internet Inspection Request from: Tina Payne p/s u/g rec ok, no esc this project
ELE08-01862 Permanent Service10/21/200810/21/200810/21/2008 1:17:20 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Jim Williams p/s u/g n ok
ELE08-02837 Electrical Rough-In10/21/200810/21/200810/21/2008 12:44:50 PMPFAIL
ready for rough in Phone #: ###-#### Internet Inspection Request from: gary batten called structural and electrician, BCC shall obtain building permit, NEC 210.52 shall provide required outlet spacing, 300.4(A) edge of bored holes shall be 1 1/4" from edge of framing members, no esc this project
ELE08-02762 Rough-In Permanent Service10/21/200810/21/200810/21/2008 10:55:32 AMAFAIL
Scheduled by a contractor via Hello! on 10/21/2008 at 7:00:20 AM. Contact: ###-####. called contractor, NEC 310.16 conductor size too small to panel, no esc this project
ELE08-01632 Final10/20/200810/21/200810/21/2008 10:03:57 AMACANC
Phone #: ###-#### Internet Inspection Request from: Jenni Keller wrong type request see ri
ELE08-01632 Electrical Rough-In10/21/200810/21/200810/21/2008 10:03:00 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Jenni Keller corrections not made, fee due, called contractor, told to call in correctly next time
ELE08-02752 Final10/21/200810/21/200810/21/2008 9:36:46 AMAPASS
please call me so that I can insure that someone is there to let you in Thanks Shaun ###-#### Phone #: ###-#### Internet Inspection Request from: Shaun Kirkman ok to final, no card to sign, no esc this project
ELE08-02801 Electrical Rough-In10/20/200810/21/200810/21/2008 9:20:00 AMAPASS
Not sure what to call this inspection. It is for the trench for light pole in parking lot. Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot u/g for parking lot light only ok to cover
ELE08-02851 Electrical Rough-In10/20/200810/21/200810/21/2008 8:51:58 AMAPASS
mike Phone #: ###-#### - please call for access walls only ok to cover, south east building, west side, no esc this project
ELE08-02557 Final10/20/200810/21/200810/21/2008 8:24:59 AMAPART
4 parking lot pole lights. Phone #: ###-#### Internet Inspection Request from: Joe Thomas light poles ok, service disconnects require 2 ground rods, called contractor, he will call back for p/s if ipco needs sticker for p/s, no esc this project