FIR08-00446
| FIR-Aging Inspection | 10/21/2008 | 10/21/2008 | 10/21/2008 4:58:33 PM | | DONE |
|
|
Work in progress, construction underway.
|
FIR08-00624
| INSP-Sprinkler Rough-in | 10/20/2008 | 10/21/2008 | 10/21/2008 4:57:54 PM | P | PART |
|
|
Rough in inspection passed, two missing hangers added while on site, need inspection for tenting when complete, riser is not yet finished, noted heads not installed at some locations.
|
BLD07-00954
| FIRE-Final Inspection | 10/21/2008 | 10/21/2008 | 10/21/2008 4:55:25 PM | P | NR |
|
|
Pending request for fire alarm permit doc final.
|
FIR08-00328
| INSP-Sprinkler Rough-in | 10/21/2008 | 10/21/2008 | 10/21/2008 4:54:35 PM | P | PART |
|
|
The remainder of OH fire sprinkler work at the 2nd floor tenant remodel is okay for cover.
|
FIR07-01051
| INSP-Sprinkler Rough-in/Hydro | 10/21/2008 | 10/21/2008 | 10/21/2008 4:53:28 PM | P | PART |
|
|
See locations on approved plans sheet FP5 and FP8 for the 1st floor electrical room and 2nd floor media center; hanger attatchments only approved for cover. NOTE: Hydrostatic testing for the underground supply line and remote FDC piping also completed and passed.
|
BLD07-00421
| FIRE-Final Inspection | 10/20/2008 | 10/21/2008 | 10/21/2008 4:47:40 PM | A | PASS |
|
|
Life safety passed under condition that manual thumbturns at three exit doors need to be removed prior to structural final as discussed with contractor. No signature card available on site.
|
BLD08-01657
| FIRE-Final Inspection | 10/20/2008 | 10/21/2008 | 10/21/2008 4:44:47 PM | A | FAIL |
|
|
Door hardware at the elevator lobby egress needs to be changed, provide means for testing the two duct smoke detection devices for unit shutdown and remote annunciator functionality, remiander of life safety items are satisfactory.
|
FIR07-01051
| INSP-Supply line flush | 10/20/2008 | 10/21/2008 | 10/21/2008 4:42:03 PM | A | PART |
|
|
UG fire supply line and remote FDC piping flush completed acceptable.
|
FIR06-00621
| INSP-Alarm Testing | 10/20/2008 | 10/21/2008 | 10/21/2008 4:41:05 PM | A | PART |
|
|
Testing completed for 2nd floor mechanical area duct smoke detection devices, noted sample tube at one location missing end plug, three units not available for shutdown, also tested flow switch and two DD at the penthouse mechanical room. Additional SD at the 1st floor corridor tested okay.
|