Inspections for the day of: Tuesday, October 21, 2008.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00446 FIR-Aging Inspection10/21/200810/21/200810/21/2008 4:58:33 PM DONE
Work in progress, construction underway.
FIR08-00624 INSP-Sprinkler Rough-in10/20/200810/21/200810/21/2008 4:57:54 PMPPART
Rough in inspection passed, two missing hangers added while on site, need inspection for tenting when complete, riser is not yet finished, noted heads not installed at some locations.
BLD07-00954 FIRE-Final Inspection10/21/200810/21/200810/21/2008 4:55:25 PMPNR
Pending request for fire alarm permit doc final.
FIR08-00328 INSP-Sprinkler Rough-in10/21/200810/21/200810/21/2008 4:54:35 PMPPART
The remainder of OH fire sprinkler work at the 2nd floor tenant remodel is okay for cover.
FIR07-01051 INSP-Sprinkler Rough-in/Hydro10/21/200810/21/200810/21/2008 4:53:28 PMPPART
See locations on approved plans sheet FP5 and FP8 for the 1st floor electrical room and 2nd floor media center; hanger attatchments only approved for cover. NOTE: Hydrostatic testing for the underground supply line and remote FDC piping also completed and passed.
BLD07-00421 FIRE-Final Inspection10/20/200810/21/200810/21/2008 4:47:40 PMAPASS
Life safety passed under condition that manual thumbturns at three exit doors need to be removed prior to structural final as discussed with contractor. No signature card available on site.
BLD08-01657 FIRE-Final Inspection10/20/200810/21/200810/21/2008 4:44:47 PMAFAIL
Door hardware at the elevator lobby egress needs to be changed, provide means for testing the two duct smoke detection devices for unit shutdown and remote annunciator functionality, remiander of life safety items are satisfactory.
FIR07-01051 INSP-Supply line flush10/20/200810/21/200810/21/2008 4:42:03 PMAPART
UG fire supply line and remote FDC piping flush completed acceptable.
FIR06-00621 INSP-Alarm Testing10/20/200810/21/200810/21/2008 4:41:05 PMAPART
Testing completed for 2nd floor mechanical area duct smoke detection devices, noted sample tube at one location missing end plug, three units not available for shutdown, also tested flow switch and two DD at the penthouse mechanical room. Additional SD at the 1st floor corridor tested okay.