BLD08-00457
| FIRE-Alarm Testing | 10/20/2008 | 10/21/2008 | 10/22/2008 2:40:00 PM | P | PASS |
|
|
testing for duct detectors passed
|
FIR08-00657
| INSP-Sprinkler Rough-in | 10/20/2008 | 10/21/2008 | 10/21/2008 3:33:38 PM | P | PASS |
|
|
The previous deficiencies have been corrected. The sprinkler piping can be covered.
|
FIR08-00628
| INSP-Sprinkler Rough-in | 10/21/2008 | 10/21/2008 | 10/21/2008 3:18:04 PM | P | PASS |
|
|
See the city approved plans for locations where the sprinkler piping is ok to cover.
|
FIR08-00510
| INSP-Final Inspection | 10/20/2008 | 10/21/2008 | 10/21/2008 3:04:29 PM | P | PASS |
|
|
permit finaled
|
BLD08-02156
| FIRE-Final Inspection | 10/20/2008 | 10/21/2008 | 10/21/2008 1:26:50 PM | A | PART |
|
|
A temporary occupancy was given until the sprinkler coverage issues have been addressed. This work will require a separate permit.
|
BLD07-02596
| FIRE-Final Inspection | 10/20/2008 | 10/21/2008 | 10/21/2008 10:12:24 AM | A | FAIL |
|
|
Provide fire dept access roads with the required 20' min width as per the review comments. See IFC 503.2.1. Provide fire extinguishers as per review comment #5. Provide exit signs and emergency lighting per review notes 13, 14 and drawing sheets E1.0 and E2.0L. Provide panic hardware at gates as per drawing sheet A1.1. The maglock at door 100 must meet the requirements of IFC 1008.1.3.4 and be tested. Repair the already installed exit signs and emergency lights. Provide single action hardware, (remove keyed lock) on door 102. Remove locking hardware at door 110A. Provide occupant load signs as per the review comments and drawings. Provide a building address.
|