FIR10-00039
| FIR-Aging Inspection | 10/21/2013 | 10/21/2013 | 10/29/2013 9:20:31 AM | | NR |
|
|
I left voice message for Mary for a follow up.
|
FIR13-00497
| INSP-Sprinkler Rough-in | 10/21/2013 | 10/21/2013 | 10/21/2013 3:45:28 PM | P | PASS |
|
|
ok to cover piping above lay-in tile areas
|
FIR13-00339
| INSP-Sprinkler Rough-in | 10/21/2013 | 10/21/2013 | 10/21/2013 3:29:31 PM | P | PASS |
|
|
Sprinkler piping is ok to cover. Tenting is approved. I noted two heads located less than the required 8'. Change will be verified at the final.
|
BLD12-01772
| FIRE-Final Inspection | 10/18/2013 | 10/21/2013 | 10/21/2013 3:06:39 PM | P | FAIL |
|
|
Repaair the two exit sign/emergency lights as noted and discuss with plan review if there is a need to resubmit plans showing the two small rooms, one of which cntains two 50 gallon drums of flammable liquids.
|
FIR13-00483
| INSP-Final Inspection | 10/18/2013 | 10/21/2013 | 10/21/2013 2:57:11 PM | P | PASS |
|
|
Permit finaled
|
BLD13-02187
| FIRE-Final Inspection | 10/21/2013 | 10/21/2013 | 10/21/2013 1:32:52 PM | P | PASS |
|
|
Life safety passed.
|
FIR13-00537
| INSP-Final Inspection | 10/21/2013 | 10/21/2013 | 10/21/2013 1:32:16 PM | P | PASS |
|
|
Permit finaled
|
FIR13-00493
| INSP-Final Inspection | 10/21/2013 | 10/21/2013 | 10/21/2013 12:13:42 PM | A | PASS |
|
|
permit finaled
|
FIR13-00565
| INSP-Sprinkler Rough-in | 10/18/2013 | 10/21/2013 | 10/21/2013 10:52:01 AM | A | PASS |
|
|
The underground supply line is ok for cover.
|
BLD13-01527
| FIRE-Final Inspection | 10/18/2013 | 10/21/2013 | 10/21/2013 10:37:08 AM | A | FAIL |
|
|
Need ADA approved hardware for the pocket doors and the project related fire alarm permit finaled.
|
FIR13-00567
| INSP-Final Inspection | 10/18/2013 | 10/21/2013 | 10/21/2013 10:34:23 AM | A | FAIL |
|
|
All items ok except the strobes do not flash as required per NFPA 72 18.5.2.1 (There was a timeed three second delay between some flashes)
|
BLD13-02159
| FIRE-Final Inspection | 10/17/2013 | 10/21/2013 | 10/21/2013 8:28:25 AM | A | FAIL |
|
|
Project not ready for a final inspection. Matt just wanted a conference on the "art of shaving" tenant space.
|
BLD13-02208
| FIRE-Final Inspection | 10/18/2013 | 10/21/2013 | 10/21/2013 8:27:13 AM | A | PART |
|
|
A temporary occupancy is being given with scotts approval until the revised wall/exiting plan is resubmitted for tims review. All other items passed.
|
BLD13-02187
| FIRE-Final Inspection | 10/20/2013 | 10/21/2013 | 10/21/2013 8:24:44 AM | A | FAIL |
|
|
Need city approved plans, sticker at main exit, tag on fire extinguisher, battery backup for the exit sign at the main exit and approved single action hardware on the north exit door.
|
BLD13-01052
| FIRE-Final Inspection | 10/18/2013 | 10/21/2013 | 10/18/2013 3:07:37 PM | A | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Ami Tracy Inspection cancelled from web by: Ami Tracy
|