ELE14-02095
| Electrical Rough-In | 10/20/2014 | 10/21/2014 | 10/21/2014 4:17:34 PM | P | PASS |
|
|
James Phone #: ###-#### r/i ok north exterior walls and soffits
|
ELE13-01291
| Electrical Rough-In | 10/20/2014 | 10/21/2014 | 10/21/2014 3:49:00 PM | P | PART |
|
|
4th level soffit area rough in. Phone #: ###-#### Inspection requested via web by Tom Betty level 4 soffits and ceiling r/i ok see inspector set for exact areas
|
ELE13-01291
| Electrical Rough-In | 10/20/2014 | 10/21/2014 | 10/21/2014 3:46:32 PM | A | PART |
|
|
Level 5 rough in for Brandon. Phone #: ###-#### Inspection requested via web by Tom Betty level 5 helix- r/i soffits and walls ok level 6 helix- columns and u. ground between columns only r/i ok see inspector set
|
ELE14-02507
| Final | 10/21/2014 | 10/21/2014 | 10/21/2014 2:44:41 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by kendall bender 210.8(A)(6)-All 120volt receptacles serving countertop in kitchen shall have GFCI protection, 210.8(A)7- laundry where receptacles are within 6 ' of sink shall have GFCI protection. 300.5-120 volt feed to existing garage unknown depth requires GFCI protection
|
ELE14-02804
| Final | 10/21/2014 | 10/21/2014 | 10/21/2014 1:32:24 PM | P | PASS |
|
|
Please call Jesse 1/2 hr. ahead of time so he can meet the inspector on-site to go over the job. Phone #: ###-#### Inspection requested via web by Matthew Dunay final ok for roughed in solar wiring only for future.
|
ELE14-02804
| Electrical Rough-In | 10/21/2014 | 10/21/2014 | 10/21/2014 1:30:44 PM | P | PASS |
|
|
Please call Jesse 1/2 hr. ahead of time so he can meet the inspector on-site to go over the job. Phone #: ###-#### Inspection requested via web by Matthew Dunay r/i ok future solar for 2 invertors ok
|
ELE14-02898
| Final | 10/21/2014 | 10/21/2014 | 10/21/2014 12:39:11 PM | P | CANC |
|
|
This is a final inspection, contact person is Justin Metcalf. You will need to call ahead of time as he will not be on job site, his number is ###-####. Thanks and have a great day. Phone #: ###-#### Inspection requested via web by Laura Longshaw cancelled will reschedule
|
ELE10-00565
| ELE-Aging Inspection | 10/21/2014 | 10/21/2014 | 10/21/2014 12:37:13 PM | | DONE |
|
|
too busy
|
ELE14-02780
| Electrical Rough-In | 10/20/2014 | 10/21/2014 | 10/21/2014 12:36:50 PM | P | PASS |
|
|
Robert. Phone #: ###-#### Inspection requested via web by Sean DeLacy r/i ok s.west corridor
|
ELE14-01385
| Electrical Rough-In | 10/20/2014 | 10/21/2014 | 10/21/2014 11:43:20 AM | A | PASS |
|
|
Ground ring inspection. Phone #: ###-#### Inspection requested via web by Tom Betty Annex bldg. grounding electrode from footing parrellel with Front street ok to cover
|
ELE14-02926
| Electrical Rough-In | 10/21/2014 | 10/21/2014 | 10/21/2014 10:35:18 AM | A | PASS |
|
|
UNIT 1B-PLEASE CALL AHEAD ###-####-WOULD LIKE TO MEET YOU THERE Phone #: ###-#### Inspection requested via web by John VanZandt r/i ok
|
ELE14-02407
| Final | 10/20/2014 | 10/21/2014 | 10/21/2014 10:04:15 AM | A | PASS |
|
|
Key in front outlet Phone #: ###-#### Inspection requested via web by TOM BICANDI final ok
|
GCE14-00177
| GCE-Final | 10/20/2014 | 10/21/2014 | 10/21/2014 9:27:58 AM | A | PASS |
|
|
Warren ###-#### final ok
|
GCE14-00146
| GCE-Final | 10/20/2014 | 10/21/2014 | 10/21/2014 9:04:54 AM | A | PASS |
|
|
Jeff ###-#### please call for access if needed final ok
|
GCE14-00169
| GCE-Rough-In | 10/20/2014 | 10/21/2014 | 10/21/2014 8:41:03 AM | A | NH |
|
|
Chad ###-#### no access
|