ELE19-04031
| Electrical Rough-In | 10/18/2019 | 10/21/2019 | 10/21/2019 3:49:58 PM | P | PASS |
|
|
Contact: Rob Lawrence Phone #: ###-#### Inspection requested via web by Deb Gooden Discussed the existing conduits and raceways exposed during remodel that are not up to todays code. If existing are not used as part of this remodel and there are not life safety issuesthey are ok to remain as originally installed. If used in any way they shall conform to today code. BCC 4-05-32- Code violations not to be retained. 110.26- Work clearance shall be provided for HVAC disconnect for electric furnace located in a small enclosed space large enough for unit only and disconnect located above unit with 480 volt circuit present. Coffee bar walls only rough in ok cover
|
ELE19-00602
| Electrical Rough-In | 10/21/2019 | 10/21/2019 | 10/21/2019 2:53:26 PM | P | PASS |
|
|
5th Floor PT deck cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Level noted on north and west sides pour rough in ok cover.
|
ELE19-03863
| Final | 10/21/2019 | 10/21/2019 | 10/21/2019 2:23:29 PM | P | FAIL |
|
|
Call me if pad lock is locked. Phone #: ###-#### Inspection requested via web by Kevin Burke 210.8(B)- All outdoor receptacle outlets less than 150 volts to ground up to 50 amp shall have GFCI protection. 30 amp, 2pole twist lock shall have GFCI protection.
|
ELE19-03973
| Permanent Service | 10/18/2019 | 10/21/2019 | 10/21/2019 11:46:09 AM | A | FAIL |
|
|
The lock box code 1037. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 110.24- Available fault current shall be posted prior to permanent service inspection with value and date calculated. 10K rated devices installed. All existing electrical disconnected, only temp power on exterior at rear of building.
|
ELE19-03633
| Rough-In Permanent Service | 10/18/2019 | 10/21/2019 | 10/21/2019 11:08:24 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Sherry Allen Service only. Available fault current not posted but verified with contractor at 31k available inrush current. Will post by final. p/s u/g n ok
|
ELE19-03983
| Rough-In Permanent Service | 10/18/2019 | 10/21/2019 | 10/21/2019 9:55:24 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Rough in ok cover p/s u/g n ok
|