Inspections for the day of: Monday, October 21, 2019.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04031 Electrical Rough-In10/18/201910/21/201910/21/2019 3:49:58 PMPPASS
Contact: Rob Lawrence Phone #: ###-#### Inspection requested via web by Deb Gooden
Discussed the existing conduits and raceways exposed during remodel that are not up to todays code. If existing are not used as part of this remodel and there are not life safety issuesthey are ok to remain as originally installed. If used in any way they shall conform to today code.
BCC 4-05-32- Code violations not to be retained. 110.26- Work clearance shall be provided for HVAC disconnect for electric furnace located in a small enclosed space large enough for unit only and disconnect located above unit with 480 volt circuit present.
Coffee bar walls only rough in ok cover
ELE19-00602 Electrical Rough-In10/21/201910/21/201910/21/2019 2:53:26 PMPPASS
5th Floor PT deck cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Level noted on north and west sides pour rough in ok cover.
ELE19-03863 Final10/21/201910/21/201910/21/2019 2:23:29 PMPFAIL
Call me if pad lock is locked. Phone #: ###-#### Inspection requested via web by Kevin Burke 210.8(B)- All outdoor receptacle outlets less than 150 volts to ground up to 50 amp shall have GFCI protection. 30 amp, 2pole twist lock shall have GFCI protection.
ELE19-03973 Permanent Service10/18/201910/21/201910/21/2019 11:46:09 AMAFAIL
The lock box code 1037. If you have any questions please feel free to contact Andrew ###-####. Thanks!! Phone #: ###-#### Inspection requested via web by Clayton Morgan 110.24- Available fault current shall be posted prior to permanent service inspection with value and date calculated. 10K rated devices installed. All existing electrical disconnected, only temp power on exterior at rear of building.
ELE19-03633 Rough-In Permanent Service10/18/201910/21/201910/21/2019 11:08:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Sherry Allen
Service only. Available fault current not posted but verified with contractor at 31k available inrush current. Will post by final. p/s u/g n ok
ELE19-03983 Rough-In Permanent Service10/18/201910/21/201910/21/2019 9:55:24 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt
Rough in ok cover p/s u/g n ok