Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02412 ELE-Aging Inspection10/21/201910/21/201910/28/2019 6:05:14 AM DONE
Schedule a final inspection.
ELE19-03682 Electrical Rough-In10/21/201910/21/201910/21/2019 2:56:24 PMPPASS
Shaun Phone #: ###-#### Ok cover mstr floor heat
ELE19-02313 Final10/21/201910/21/201910/21/2019 1:30:53 PMPPASS
Final for service only. Phone #: ###-#### Inspection requested via web by Garrett Collins Ok final. Intersystem installed, main breaker only, no other breakers.
ELE19-01596 Final10/21/201910/21/201910/21/2019 12:54:40 PMPPASS
Lee Phone #: ###-#### Ok final ceiling fan back porch.
ELE19-04049 Permanent Service10/21/201910/21/201910/21/2019 12:04:06 PMPPASS
Phone #: ###-#### Inspection requested via web by Garrett Collins p/s o/h rec ok
ELE19-00005 Final10/21/201910/21/201910/21/2019 11:24:38 AMAPASS
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden Ok final coffee bar in plaza.
ELE19-01489 Electrical Rough-In10/18/201910/21/201910/21/2019 11:01:42 AMAPASS
Wall cover in area D. Toby is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen Ok cover Area D walls. Highlighted and noted on prints.
ELE18-04721 Final10/18/201910/21/201910/21/2019 10:15:46 AMAPASS
Swimming pool electrical final Phone #: ###-#### Inspection requested via web by Lars Johnson Ok final.
ELE19-04035 Permanent Service10/18/201910/21/201910/21/2019 9:11:28 AMAFAIL
Keeley Phone #: ###-####
1. Grounding electrode system needs updated. Minimum #6 copper, and 2 ground rods atleast 6' apart.
2. Left phase conductor in outside disconnect needs checked. Looks like insulation is split before landing in breaker.
3. Bushing needed in top right portion of inside panel.