ELE19-03960
| Final | 10/14/2019 | 10/21/2019 | 10/21/2019 2:42:25 PM | P | NR |
|
|
Please come as late as possible and call ahead Phone #: ###-#### Inspection requested via web by Kyle Dillon....will request inspection once power re-energized...verify multi-branch circuits on 2 pole breakers 4 qty
|
ELE19-03960
| Electrical Rough-In | 10/14/2019 | 10/21/2019 | 10/21/2019 2:41:04 PM | P | NR |
|
|
Please come as late as possible and call ahead Phone #: ###-#### Inspection requested via web by Kyle Dillon...will request once power restalled...verify 2 pole breakers on multi-branch circuits
|
ELE19-03960
| Permanent Service | 10/21/2019 | 10/21/2019 | 10/21/2019 2:39:16 PM | P | PASS |
|
|
Please come as late as possible and call ahead Phone #: ###-#### Inspection requested via web by Kyle Dillon...p/s u/g reconnect ok
|
ELE19-03948
| Electrical Rough-In | 10/18/2019 | 10/21/2019 | 10/21/2019 2:16:35 PM | P | PASS |
|
|
Please call ahead Phone #: ###-#### Inspection requested via web by Kyle Dillon... rough ok to cover dwnstairs-closet, office, and sitting rm upstairs-new bedroom and utillity/craft room
|
ELE19-04000
| Final | 10/21/2019 | 10/21/2019 | 10/21/2019 1:37:15 PM | P | PASS |
|
|
Final inspection please. Thank you and have a bless week!!!! Phone #: ###-#### Inspection requested via web by Kyle Lott... moving of main panel (existing) to new electrical rm location and transformer feeding 100A existing panel...safing off of demissing walls as needed...no new wiring for tenant improvement on this permit...permit to be pulled by another contractor for tenant wiring...job complete...ok to final
|
ELE19-03354
| Final | 10/18/2019 | 10/21/2019 | 10/21/2019 12:51:01 PM | P | PASS |
|
|
final on swimming pool owner will be home Phone #: ###-#### Inspection requested via web by Kevin Koomler...ok to final
|
ELE19-03161
| Final | 10/21/2019 | 10/21/2019 | 10/21/2019 11:05:57 AM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by jamie berg...correction made...ok to final
|
ELE19-03194
| Final | 10/18/2019 | 10/21/2019 | 10/21/2019 10:40:29 AM | A | PASS |
|
|
Kyle Phone #: ###-####... permit holders scope of work complete wiring for building complete future permit required for equipment ok to final...no card on site
|
ELE19-03980
| Final | 10/15/2019 | 10/21/2019 | 10/21/2019 10:38:01 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Steven Ragan...
1) OCPD shall not exceed name plate 2) panel shall be properly labelled...408.4 3) proper connector shall be installed on wiring...outside unit to inside unit..110.3,110.8
|
ELE19-04045
| Electrical Rough-In | 10/21/2019 | 10/21/2019 | 10/21/2019 9:36:05 AM | A | FAIL |
|
|
LOCK BOX LOCATED #101 CODE 7777 KEY FOR ALL UNITS Phone #: ###-#### Inspection requested via web by Hidajet Zahic... 1) exterior lights need boxes installed on NM cable 2) attic shall have a service outlet and light for furnace...unable to verify attic access location...light switch shall be located at immediate entry into attic
|
ELE19-04044
| Electrical Rough-In | 10/21/2019 | 10/21/2019 | 10/21/2019 9:32:29 AM | A | FAIL |
|
|
LOCK BOX LOCATED #101 CODE 7777 KEY FOR ALL UNITS Phone #: ###-#### Inspection requested via web by Hidajet Zahic... 1) exterior lights need boxes installed on NM cable 2) attic access service light and outlet need complete installation...lamp in keyless and plate on outlet/switch 2 gang
|
ELE19-04046
| Electrical Rough-In | 10/21/2019 | 10/21/2019 | 10/21/2019 9:29:39 AM | A | FAIL |
|
|
LOCK BOX LOCATED #101 CODE 7777 KEY FOR ALL UNITS Phone #: ###-#### Inspection requested via web by Hidajet Zahic... 1) exterior lights shall have box istalled on NM cable 2) attic service light and outlet need completed... lamp installed in keyless and plate on switch/outlet 2 gang
|