ELE00-01637
| Final | 10/21/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | A | PASS |
|
|
###-#### FRANK PLEASE CAAL FOR ACCESS ok 10/22/2002 11:31:18 AM
|
ELE02-00732
| Final | 10/21/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | A | FAIL |
|
|
call 1st before insp -dave; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie 210.52(C) outlet needed left of sink, 210.52(A) outlet required in dinning rm window wall, needs gfci for island counter, where grd outlets are on ungrd circuit, outlets in unfinished basement, adn 210.70 3 way for stairs met with contractor 10/22/2002 11:07:27 AM
|
ELE02-03271
| Electrical Rough-In | 10/21/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | A | NH |
|
|
basement and garage ###-#### notice posted called left message 10/22/2002 12:36:46 PM
|
ELE02-03166
| Final | 10/21/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|
ELE98-02307
| Electrical Rough-In | 10/21/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | A | FAIL |
|
|
###-#### ERIC corrections not made still needs 6 inches free length of conductor ged wires cut short only 11/2 to 2 inches long 10/22/2002 12:26:07 PM
|
ELE02-02842
| Final | 10/22/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 10/22/2002 at 07:01:16. Contact: ###-####. ok 10/22/2002 1:22:21 PM
|
ELE02-03242
| Rough-In Permanent Service | 10/22/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | P | PASS |
|
|
###-#### met with contractor for spacing of outlets that serve kit, and dinning counters , he will adjust for proper spacing, and move phone and data from below house panel and p/s all 4 units ok for r/i
p/s u/g new ok 10/22/2002 4:15:03 PM
|
ELE01-00461
| Electrical Rough-In | 10/22/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | P | PART |
|
|
DAN ###-#### conference ok 10/22/2002 3:14:30 PM
|
ELE02-03152
| Permanent Service | 10/22/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | P | PASS |
|
|
###-#### cover for electrode ok
p/s o/h new ok 10/22/2002 4:38:37 PM
|
ELE02-00871
| Electrical Rough-In | 10/22/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | P | PART |
|
|
cor. posted for r/i 225.18(1) shall provide required clearence for both o/h drops to garage,225.30 provide disconnects at garage, 250.32 install grd rods at garage or carry equip grd to garage, 210.70 install outside light for garage entry door met with contractor
|
ELE02-00871
| Permanent Service | 10/22/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | P | PASS |
|
|
p/s o/h rec. ok
|