ELE02-03225
| Final | 10/21/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | A | NR |
|
|
###-#### 10/21/2002 2:11:56 PM
Had conf. 10/22/2002 9:56:12 AM
|
ELE02-03077
| Temporary Service | 10/21/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | A | PASS |
|
|
###-####
T/S O/H Ok 10/22/2002 11:30:39 AM
|
ELE01-03949
| Final | 10/21/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | A | FAIL |
|
|
Contact: ###-####.
410.8 Luminaires (Fixtures) in Clothes Closets.
(C) Luminaire (Fixture) Types Not Permitted.
For a final inspection in the city of Boise all of the electrical must be complete and in working order. This includes the installation of lamps in all lighting fixtures.
314.17 Conductors Entering Boxes, Conduit Bodies, or Fittings.
(B) Metal Boxes and Conduit Bodies.
110.12 Mechanical Execution of Work.
(A) Unused Openings.
II. 600 Volts, Nominal, or Less
110.26 Spaces About Electrical Equipment.
Sufficient access and working space shall be provided and maintained about all electric equipment
(1) Indoor. Indoor installations shall comply with 110.26(F)(1)(a) through (d).
210.70 Lighting Outlets Required.
Lighting outlets shall be installed where specified in 210.70(A), (B), and (C).
210.52 Dwelling Unit Receptacle Outlets.
Receptacle outlets required by this section shall be in addition to any receptacle that is part of a luminaire (lighting fixture) or appliance, located within cabinets or cupboards
(C) Countertops. In kitchens and dining rooms of dwelling units, receptacle outlets for counter spaces shall be installed in accordance with 210.52(C)(1) through (5).
330.30 Securing and Supporting. (C) At Terminations. Cables containing four or fewer conductors, sized no larger than 10 AWG, shall be secured within 300 mm (12 in.) of every box,
10/22/2002 11:32:15 AM
|
ELE00-04736
| Final | 10/21/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | A | PASS |
|
|
###-#### key under mat at back door
for tomorrow
|
ELE02-03276
| Rough-In Permanent Service | 10/22/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | A | PASS |
|
|
###-####
P/S U/G N Ok 10/22/2002 2:57:57 PM
|
ELE02-00442
| Final | 10/22/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | P | PASS |
|
|
861-46+92 jean
|
ELE02-03147
| Rough-In Permanent Service | 10/22/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/22/2002 at 07:44:50. Contact: ###-####.
No electrode and protection of romex 10/22/2002 1:32:41 PM
|
ELE02-02870
| Rough-In Permanent Service | 10/22/2002 | 10/22/2002 | 10/22/2002 12:00:00 AM | P | NR |
|
|
late as possible; Phone #: ###-#### Internet Inspection Request from: Rita DeYoung
|