FIR07-00441
| INSP-Final Inspection | 10/19/2007 | 10/22/2007 | 10/23/2007 11:51:54 AM | A | PART |
|
|
Tested cleanroom notification-noted two areas lacking sufficient visual coverage, need to program voltage monitoring at the elevator for a supervisory condition, retested c/n items from previous inspection.
|
FIR07-00567
| INSP-Final Inspection | 10/16/2007 | 10/22/2007 | 10/22/2007 3:27:26 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD07-00292
| FIRE-Conference | 10/22/2007 | 10/22/2007 | 10/22/2007 1:28:43 PM | P | DONE |
|
|
Conference regarding contractors intent to pursue a partial approval of fire permits for temporary occupancy approval.
|
FIR07-00425
| INSP-Sprinkler Rough-in/Hydro | 10/19/2007 | 10/22/2007 | 10/22/2007 1:18:25 PM | A | PART |
|
|
OH hydrostatic test for the 5th floor passed, overhead rough-in for the 5th floor completed- noted SW heads at the elevator and trash chute are not yet installed, heads at patios are not installed pending AFSA ruling, need cold cavity protection prior to ceiling cover.
|
FIR07-00716
| INSP-Sprinkler Rough-in | 10/22/2007 | 10/22/2007 | 10/22/2007 12:41:21 PM | P | CANC |
|
|
don Phone #: ###-####
|
FIR07-00601
| INSP-Sprinkler Rough-in | 10/22/2007 | 10/22/2007 | 10/22/2007 12:40:48 PM | P | PART |
|
|
OH rough-in completed okay, one head relocated while on site, missing escutcheon at the vestibule also installed, final pending placement of field ceiling tile.
|
BLD07-00625
| FIRE-Final Inspection | 10/19/2007 | 10/22/2007 | 10/22/2007 12:38:59 PM | A | PASS |
|
|
Fire life safety is satisfactory pending addition of exit signs as indicated on approved plans and per discussion, exit signs to be completed prior to structural final.
|
FIR07-00511
| INSP-Final Inspection | 10/22/2007 | 10/22/2007 | 10/22/2007 12:36:53 PM | P | PASS |
|
|
Corrections verified for completion, inspection passed, permit finaled.
|
BLD07-01537
| FIRE-Final Inspection | 10/19/2007 | 10/22/2007 | 10/22/2007 12:31:05 PM | A | FAIL |
|
|
Need project related fire sprinkler permit final prior to life safety, need to relocate exit signs as discussed.
|
BLD07-02244
| FIRE-Final Inspection | 10/17/2007 | 10/22/2007 | 10/22/2007 10:46:59 AM | A | PART |
|
|
3rd floor SE quadrant fire life safety passed, noted one missing EM light and one exit sign to be relocated, will verifiy corrections at next site visit.
|
BLD06-01188
| FIRE-Final Inspection | 10/19/2007 | 10/22/2007 | 10/22/2007 10:44:20 AM | A | PART |
|
|
Fire life safety for the 3rd floor SE quadrant is acceptable.
|
FIR06-00595
| INSP-Alarm Testing | 10/19/2007 | 10/22/2007 | 10/22/2007 10:43:18 AM | A | PART |
|
|
3rd floor SE quad fire alarm system modifications passed field testing.
|
FIR07-00331
| FIR-Aging Inspection | 10/22/2007 | 10/22/2007 | 10/22/2007 8:41:53 AM | | DEFR |
|
|
wip
|
FIR07-00694
| INSP-Conference | 10/19/2007 | 10/22/2007 | | A | |
|
|
PIV issue
|