FIR07-00726
| INSP-Sprinkler Rough-in | 10/22/2007 | 10/22/2007 | 10/22/2007 4:27:42 PM | P | FAIL |
|
|
See the city approved plans for the locations of the deficiencies. The sprinkler piping is not ok to cover.
|
FIR07-00756
| INSP-Sprinkler Rough-in | 10/22/2007 | 10/22/2007 | 10/22/2007 4:25:47 PM | P | PASS |
|
|
The deficiencies have been corrected and the sprinkler piping is ok to cover. I found one overspaced head just inside of the entry vestibule. I notified Trent of this and told him I would verify the installation at the final.
|
FIR07-00806
| INSP-Final Inspection | 10/22/2007 | 10/22/2007 | 10/22/2007 4:24:04 PM | P | PASS |
|
|
Hood suppression system operated correctly
|
BLD06-02105
| FIRE-Final Inspection | 10/22/2007 | 10/22/2007 | 10/22/2007 3:04:07 PM | P | PASS |
|
|
Life safety passed
|
BLD06-02059
| FIRE-Final Inspection | 10/19/2007 | 10/22/2007 | 10/22/2007 2:51:08 PM | A | FAIL |
|
|
A manometer test is needed for the duct smoke detectors as well as actuall testing of the devices. All other items are ok.
|
FIR07-00813
| INSP-Sprinkler Rough-in | 10/19/2007 | 10/22/2007 | 10/22/2007 1:41:14 PM | A | CANC |
|
|
Cancelled per bill Phone #: ###-####
|
FIR07-00647
| INSP-Final Inspection | 10/19/2007 | 10/22/2007 | 10/22/2007 12:43:35 PM | A | PASS |
|
|
Permit finaled
|
FIR06-00778
| INSP-Final Inspection | 10/19/2007 | 10/22/2007 | 10/22/2007 11:46:28 AM | A | FAIL |
|
|
A domestic shutoff valve has been installed that is not shown on the plans or in the hydraulic calculations. Provide revised plans to the city of boise for verification of the changes. The wrong backflow has been installed. Provide heads and as-builts per review note #4. Flush the underground supply. Certify backflow.
|
FIR07-00346
| INSP-Sprinkler Rough-in | 10/18/2007 | 10/22/2007 | 10/22/2007 11:39:01 AM | A | PASS |
|
|
Underground hydro test passed
|