FIR09-00446
| FIR-Aging Inspection | 10/22/2009 | 10/22/2009 | 10/22/2009 5:01:34 PM | | DONE |
|
|
Work in progress, construction underway.
|
FIR09-00286
| INSP-Sprinkler Rough-in | 10/22/2009 | 10/22/2009 | 10/22/2009 4:58:40 PM | P | DONE |
|
|
follow up rough to cover.I would like to meet to discuss what needs to happen in order to final attached units on seperate permits.Scott Carter II ###-#### Phone #: ###-#### Internet Inspection Request from: Scott Carter II
|
BLD09-01127
| FIRE-Final Inspection | 10/22/2009 | 10/22/2009 | 10/22/2009 4:57:49 PM | P | FAIL |
|
|
See fire code review notes for details, noted missing max. occupant load sign, need to install two exit signs per approved drawings, provide two class K and one 2A10BC fire extinguishers and post as discussed, tenant addresses must match permit documents, tags at the hood suppression systems are missing, etc., discussed issues with the owner/operators on site.
|
FIR09-00519
| INSP-Final Inspection | 10/22/2009 | 10/22/2009 | 10/22/2009 4:53:34 PM | P | PASS |
|
|
Fire sprinkler permit final approved.
|
FIR09-00577
| INSP-Final Inspection | 10/22/2009 | 10/22/2009 | 10/22/2009 4:52:54 PM | P | PASS |
|
|
Fire sprinkler permit okayed for final, contractor to replace one escutcheon today as discussed.
|
BLD09-01188
| FIRE-Final Inspection | 10/22/2009 | 10/22/2009 | 10/22/2009 4:51:53 PM | P | PASS |
|
|
Vanilla life safety passed, advised contractor to apply for a certificate of occupancy request prior to tenant move in.
|
FIR09-00592
| INSP-Sprinkler Rough-in | 10/22/2009 | 10/22/2009 | 10/22/2009 4:47:15 PM | P | PART |
|
|
Fire sprinkler work per permit documents is okay for cover at apt.# 34 building 1632.
|
FIR09-00479
| INSP-Sprinkler Rough-in/Hydro | 10/22/2009 | 10/22/2009 | 10/22/2009 4:45:51 PM | A | PART |
|
|
Overhead fire sprinkler rough-in inspection passed with the exception of two locations marked on plans in need of hangers/branchline restraint, cover is not approved until tenting/insulation is completed and inspected for cold cavity protection, be aware of light fixure obstructions that may develop depending on equipment installed, minor field mods. in pipe runs okayed due to 20% cushion in calcs, riser is not yet built.
|
BLD09-01837
| FIRE-Final Inspection | 10/21/2009 | 10/22/2009 | 10/22/2009 9:46:14 AM | A | PASS |
|
|
Items on correction notice verified for completion, life safety finaled.
|