Inspections for the day of: Monday, October 22, 2012.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR11-00624 FIR-Aging Inspection10/22/201210/22/201210/23/2012 8:32:38 AM NR
Mike is going to follow up on the project status
BLD12-01946 FIRE-Final Inspection10/22/201210/22/201210/22/2012 3:49:53 PMPCANC
Life safety passed.
FIR12-00205 INSP-Sprinkler Rough-in/Hydro10/22/201210/22/201210/22/2012 3:34:37 PMPPASS
Underground hydro test passed.
FIR12-00205 INSP-Supply line flush10/22/201210/22/201210/22/2012 3:33:12 PMPCANC
To be rescheduled per Perly due to United Water not having the underground supply turn on.
BLD12-02043 FIRE-Final Inspection10/18/201210/22/201210/22/2012 2:57:14 PMPFAIL
The project related fire alarm and fire sprinkler permits need to be finaled, Knox box is required, signage on the riser room door is required, small documents/building submittal is required, repair the exit sign/emergency light at the main exit.
FIR12-00547 INSP-Final Inspection10/19/201210/22/201210/22/2012 2:48:57 PMPFAIL
The electric alarm bell has not been installed yet. Plan modifications are required for the four duct smoke detectors that were not included on the original submittal. The sample tubes currently installed are too short. Need breaker lock installed. The manual pull station installed is not the same as the submittal though it is addressable and does function.
FIR12-00477 INSP-Final Inspection10/18/201210/22/201210/22/2012 2:36:57 PMPFAIL
The outside alarm bell has not been mounted yet therefore it could not be tested by the functional test of the flow switch. Forward flush passed.
FIR12-00504 INSP-Sprinkler Rough-in10/22/201210/22/201210/22/2012 1:44:41 PMPPART
Sprinkler piping is ok to cover. Two pendant heads were overspaced but to be verified at final inspection. See approved plans for locations. Stephen was installing hanger clips due to 100psi pressure on existing system from the fire pump.
BLD12-02759 FIRE-Final Inspection10/22/201210/22/201210/22/2012 1:02:59 PMPFAIL
Provide exit signs as shown on the plans, verify that the existing emergency light is functional, provide sticker at the main exit.
BLD12-02765 FIRE-Final Inspection10/19/201210/22/201210/22/2012 11:28:13 AMAPASS
Life safety passed