FIR11-00624
| FIR-Aging Inspection | 10/22/2012 | 10/22/2012 | 10/23/2012 8:32:38 AM | | NR |
|
|
Mike is going to follow up on the project status
|
BLD12-01946
| FIRE-Final Inspection | 10/22/2012 | 10/22/2012 | 10/22/2012 3:49:53 PM | P | CANC |
|
|
Life safety passed.
|
FIR12-00205
| INSP-Sprinkler Rough-in/Hydro | 10/22/2012 | 10/22/2012 | 10/22/2012 3:34:37 PM | P | PASS |
|
|
Underground hydro test passed.
|
FIR12-00205
| INSP-Supply line flush | 10/22/2012 | 10/22/2012 | 10/22/2012 3:33:12 PM | P | CANC |
|
|
To be rescheduled per Perly due to United Water not having the underground supply turn on.
|
BLD12-02043
| FIRE-Final Inspection | 10/18/2012 | 10/22/2012 | 10/22/2012 2:57:14 PM | P | FAIL |
|
|
The project related fire alarm and fire sprinkler permits need to be finaled, Knox box is required, signage on the riser room door is required, small documents/building submittal is required, repair the exit sign/emergency light at the main exit.
|
FIR12-00547
| INSP-Final Inspection | 10/19/2012 | 10/22/2012 | 10/22/2012 2:48:57 PM | P | FAIL |
|
|
The electric alarm bell has not been installed yet. Plan modifications are required for the four duct smoke detectors that were not included on the original submittal. The sample tubes currently installed are too short. Need breaker lock installed. The manual pull station installed is not the same as the submittal though it is addressable and does function.
|
FIR12-00477
| INSP-Final Inspection | 10/18/2012 | 10/22/2012 | 10/22/2012 2:36:57 PM | P | FAIL |
|
|
The outside alarm bell has not been mounted yet therefore it could not be tested by the functional test of the flow switch. Forward flush passed.
|
FIR12-00504
| INSP-Sprinkler Rough-in | 10/22/2012 | 10/22/2012 | 10/22/2012 1:44:41 PM | P | PART |
|
|
Sprinkler piping is ok to cover. Two pendant heads were overspaced but to be verified at final inspection. See approved plans for locations. Stephen was installing hanger clips due to 100psi pressure on existing system from the fire pump.
|
BLD12-02759
| FIRE-Final Inspection | 10/22/2012 | 10/22/2012 | 10/22/2012 1:02:59 PM | P | FAIL |
|
|
Provide exit signs as shown on the plans, verify that the existing emergency light is functional, provide sticker at the main exit.
|
BLD12-02765
| FIRE-Final Inspection | 10/19/2012 | 10/22/2012 | 10/22/2012 11:28:13 AM | A | PASS |
|
|
Life safety passed
|