Inspections for the day of: Thursday, October 22, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00842 ELE-Aging Inspection10/22/201510/22/201510/26/2015 3:19:08 PM DONE
Waiting on contractor
ELE15-02315 Final10/21/201510/22/201510/22/2015 3:54:33 PMPFAIL
Final Inspection
Electrician is Darby Talbot
Contact Shari @ ###-#### for access.
Phone #: ###-#### Inspection requested via web by Cathy Duchek
210.52- Receptacle outlet spacing for a habitable room shall not exceed 6' from a receptacle measured along floor line. Buried outlet
ELE15-00089 Electrical Rough-In10/22/201510/22/201510/22/2015 2:18:13 PMPPASS
Call prior to going Phone #: 2083520355 >> Inspection requested via mobile web by Dan monzo Garage panel wall rough in ok cover
ELE15-03400 Electrical Rough-In10/22/201510/22/201510/22/2015 1:41:26 PMPFAIL
Phone #: ###-#### Inspection requested via web by daniel bibikov
300.4- NM cable shall be protected from physical damage where ran through bored holes that do not maintain 1 1/4" from framing surface.
300.13- For multiwire branch circuits continuity of a grounded conductor shall not depend on device connections.
334.30- NM cable shall not be secured with in 1 1/4" from framing surface.
ELE15-02836 Final10/22/201510/22/201510/22/2015 12:43:01 PMPPASS
READY NOW ANY ? CALL BILL ###-#### Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE15-02610 Final10/22/201510/22/201510/22/2015 12:38:42 PMPPASS
READY NOW ANY ? CALL BILL ###-#### Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE15-03397 Final10/21/201510/22/201510/22/2015 11:14:05 AMAPASS
Customer''s name is Richard and he will be home in the morning. His # is ###-####.
Call me if you have any questions.
Kevin R.E. Phone #: ###-#### Inspection requested via web by Kevin Cowgill Final ok
ELE15-03345 Final10/20/201510/22/201510/22/2015 10:36:03 AMAFAIL
Allen Phone #: ###-####
BCC 4-05-32- Code violations not to be retained.
400.8- Flexible cords shall not be used and a substitute for fixed wiring of a structure.
Cord that plugs into wall runs up wall to top of beam across to track light in living room.
ELE15-03071 Final10/21/201510/22/201510/22/2015 10:08:51 AMAFAIL
please contact jeff @ ###-#### for questions about job Phone #: ###-#### Inspection requested via web by Andrea Creek
400.8- Flexible cords shall not run through holes in walls.
400.14- Flexible cord shall be protected by bushing or fitting where ran through holes in cover. Split system
ELE15-03120 Final10/21/201510/22/201510/22/2015 9:34:08 AMAPASS
We are requesting a final inspection on this project for tomorrow in the AM. Our contact is Kory @ ###-####. Thank you,
Phone #: ###-#### Inspection requested via web by Clint Tate
Questioned location of GFCI receptacles. Contractor stated all equipment will be on counter tops so GFCI receptacles all readily accessible at time of final. Final ok
ELE15-02538 Final10/21/201510/22/201510/22/2015 9:12:30 AMAPASS
fence bonding Phone #: ###-#### Inspection requested via web by cory carman No card posted. Final ok
ELE15-03390 Temporary Service10/21/201510/22/201510/22/2015 8:30:56 AMAPASS
Phone #: ###-#### Inspection requested via web by Richard Gratiot
t/s u/g n ok