Inspections for the day of: Monday, October 22, 2018.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-02998 ELE-Aging Inspection10/22/201810/22/201810/23/2018 3:43:25 PM PASS
Drove by and posted correction notice explaining several attempts have been made to contact contractor to schedule. Dave called and explained house has sold to new owners.
ELE18-02542 Final10/22/201810/22/201810/22/2018 3:42:40 PMPFAIL
Corbin ###-#### Phone #: ###-#### Inspection requested via web by Samatha Solberg
210.8- Receptacle serving hutch counter top shall have GFCI protection.
210.52(B)(2)- Kitchen appliance circuits shall have no other outlets. Over sink and under cabinet lighting on with kitchen appliance.
210.52(C)- Receptacle outlets shall be located with in 24" of each side of kitchen sink.
314.20- Boxes mounted in a combustible wall material shall have an extension ring installed flush with surface. Appliance garage, hutch, disposal.
ELE18-03802 Electrical Rough-In10/22/201810/22/201810/22/2018 2:31:59 PMPPASS
Randy. Wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy North and west exterior office walls only rough in ok cover
ELE18-02479 Electrical Rough-In10/22/201810/22/201810/22/2018 1:47:37 PMPPART
Ceiling rough in inspection for level 10 at the One Capital building
Please contact electrician on site Jon Novak
Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek
Open office areas grid rough in ok cover
ELE18-04050 Permanent Service10/21/201810/22/201810/22/2018 10:09:51 AMAPASS
Building is unlocked. Branch panel in room C-1. Solar will be tied in at later date. #6 Bonding jumper installed between frames. Portable building is located in the backyard of the school. Phone #: ###-#### Inspection requested via web by Sean Patton
Entrance off Phillippi. p/s u/g n ok
ELE18-03977 Final10/18/201810/22/201810/22/2018 9:41:55 AMAPASS
Please call owner Brandon Rex before heading over. Thanks Phone #: ###-#### Inspection requested via web by steve ragan
Final ok
ELE18-03977 Electrical Rough-In10/22/201810/22/201810/22/2018 9:41:46 AMPPASS
Please call owner Brandon Rex before heading over. Thanks Phone #: ###-#### Inspection requested via web by steve ragan
New circuits for AC service receptacle and gas furnace rough in ok
ELE18-03623 Electrical Rough-In10/19/201810/22/201810/22/2018 7:31:02 AMACANC
Rough in new master suite addition in back. Home owner will be there. Phone #: ###-#### >> Inspection requested via web by David McClellan Inspection cancelled from web by: David McClellan