FIR02-00404
| INSP-Sprinkler Rough-in/Hydro | 10/22/2002 | 10/23/2002 | 10/23/2002 12:00:00 AM | A | FAIL |
|
|
replace the painted sprinkler heads in the front and the rear of the TI space and relocate the sprinkler heads that are closer than 4" to the walls 10/23/2002 9:55:51 AM
|
BLD02-01600
| FIRE-Final Inspection | 10/23/2002 | 10/23/2002 | 10/23/2002 12:00:00 AM | P | PASS |
|
|
fire alarm, fire sprinkler and fire/life safety finaled 10/23/2002 1:22:54 PM
|
BLD02-01601
| FIRE-Final Inspection | 10/23/2002 | 10/23/2002 | 10/23/2002 12:00:00 AM | P | PASS |
|
|
fire alarm, fire sprinkler and fire life/safety finaled 10/23/2002 1:23:13 PM
|
FIR02-00335
| INSP-Final Inspection | 10/23/2002 | 10/23/2002 | 10/23/2002 12:00:00 AM | P | PASS |
|
|
fire alarm finaled
|
FIR02-00336
| INSP-Final Inspection | 10/23/2002 | 10/23/2002 | 10/23/2002 12:00:00 AM | P | PASS |
|
|
fire alarm finaled
|
BLD01-02802
| FIRE-Final Inspection | 10/22/2002 | 10/23/2002 | 10/23/2002 12:00:00 AM | P | PASS |
|
|
fire doors operated properly and sprinkler heads are OK. The contractor will install the sprinkler head canopies when the painter is finished 10/24/2002 9:04:32 AM
|
BLD02-00691
| FIRE-Final Inspection | 10/22/2002 | 10/23/2002 | 10/23/2002 12:00:00 AM | P | FAIL |
|
|
provide a/v's in the storage turned conference rooms, relocate new duct detectors to the supply side of the duct and get the supervisory signals to the central station figured out 10/24/2002 11:07:20 AM
|