Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00463 INSP-Sprinkler Rough-in/Hydro10/23/200610/23/200610/23/2006 4:40:04 PMPFAIL
AG hydrostatic test of the wet system failed due to approx. 9psi pressure loss and a leak at one location. The dry system gauge read below 200psi at the conclusion of the test. Also noted 24hr air test needs to be completed for the dry system.
FIR06-00303 INSP-Sprinkler Rough-in/Hydro10/23/200610/23/200610/23/2006 4:34:05 PMPPART
UG hydrostatic test passed.
FIR06-00672 INSP-Sprinkler Rough-in10/23/200610/23/200610/23/2006 4:33:17 PMPPART
Partial inspection for the OH rough-in due to several areas not completed, missing EQ bracing at the end main, FDC and top of riser, drops are not installed at some locations, main and branch line installation is acceptable, noted areas at columns and soffits which may present obstructions, 130ft2 spacing to be verified when heads are cut in, UG supply and riser are not completed at this time.
FIR06-00104 INSP-Alarm Testing10/20/200610/23/200610/23/2006 4:27:45 PMPCANC
Inspection rescheduled due to time constraints.
BLD06-01634 FIRE-Final Inspection10/23/200610/23/200610/23/2006 4:27:08 PMPNR
Project is not ready for life safety final inspection.
BLD06-01953 FIRE-Final Inspection10/23/200610/23/200610/23/2006 4:26:25 PMPPASS
Visual indicator and signage above the main entry/exit to be verified at structural final.
BLD06-02515 FIRE-Conference10/20/200610/23/200610/23/2006 4:24:49 PMPDONE
On site confrence to discuss fire code review notes.
FIR06-00788 INSP-Final Inspection10/16/200610/23/200610/23/2006 4:13:51 PMPFAIL
Initiation of the hood suppression system failed to activate the building fire alarm, need to relocate the manual pull station away from the hood.
FIR06-00799 INSP-Final Inspection10/23/200610/23/200610/23/2006 12:53:10 PMPPASS
Sprinkler heads have been relocated to the proper position per scope of work, no access provided above ceiling for verification of attatchment means.
FIR06-00641 INSP-Sprinkler Rough-in10/19/200610/23/200610/23/2006 12:51:02 PMAPART
UG hydrostatic test for the fire supply line passed for building address 7960. Requested contractor to call in the correct address and permit number for this inspection activity completed today.
FIR06-00450 INSP-Sprinkler Rough-in10/20/200610/23/200610/23/2006 12:44:29 PMAFAIL
Four heads in the confrence room are supplied by a one inch line which appears to exceed the allowable calcs for this area, one area as marked on approved plans is not ready for inspection at this time.
FIR06-00090 INSP-Final Inspection10/20/200610/23/200610/23/2006 12:41:20 PMAPASS
Permitted fire sprinkler work is satisfactory, inspection passed.
FIR06-00668 INSP-Final Inspection10/17/200610/23/200610/23/2006 8:48:59 AMAFAIL
Manual pull stations at two locations within the area of work (NE and NW exits) are mounted too high, wall mounted notification devices at two hallways south of the TI area adjacent to open office areas are not in sync with the new ceiling AV's per contractor and are below min. height AFF. Provide approved plans on site at next inspection. Notified contractor to provide plans reflecting any changes on resubmittals or as-builts with inspectors approval.