Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00239 INSP-Sprinkler Rough-in/Hydro10/22/200810/23/200810/23/2008 4:37:06 PMPPART
OH rough-in for the 4th floor building #2 wet and dry system inspection completed today, noted one missing upright head at the attic system above the riser room, missing seismic bracing at dry system mains north side, tenting at the wet piping appears acceptable. Noted corridors, laundry/trash chute rooms, and star landings are not yet complete, field modifications annotated on plans for added or deleted heads, attic pockets at the north end to be entirely filled with non-combustible insulation to meet exception criteria per NFPA 13 for non-sprinklered locations.
FIR08-00364 INSP-Final Inspection10/23/200810/23/200810/23/2008 4:21:19 PMPPEND
Final pending HVAC unit startups to enable duct detector testing.
BLD07-02112 FIRE-Final Inspection10/23/200810/23/200810/23/2008 4:19:48 PMPNR
Need project related fire alarm permit final prior to building fire life safety approval.
BLD08-01363 FIRE-Final Inspection10/22/200810/23/200810/23/2008 4:17:23 PMAFAIL
Missing address numbers on the building, exit discharge lighting is not complete, missing one exit sign at the northwest exit door per clouded plan revision, need to repair EM lighting at the main office area, also need to provide means for testing the HVAC duct detectors (ie artificial smoke) for unit shutdown, inspection concluded at this time until repairs are made.
FIR08-00671 INSP-Sprinkler Rough-in10/22/200810/23/200810/23/2008 4:11:52 PMAPART
Rough-in installation at the lower mezzanine level area approved for cover-see annotations initialed with todays date on stamped plan set.
FIR06-00621 INSP-Alarm Testing10/20/200810/23/200810/23/2008 1:35:26 PMACANC
Please call 30 min prior to arrival. Phone #: ###-#### Internet Inspection Request from: Jeff Walton Inspection cancelled from web by: Jeff Walton
BLD08-01816 FIRE-Final Inspection10/22/200810/23/200810/23/2008 12:00:00 AMACANC
rob Phone #: ###-####