Inspections for the day of: Friday, October 23, 2009.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-01079 FIRE-Final Inspection10/23/200910/23/200910/23/2009 3:25:53 PMPPASS
Life safety passed.
FIR09-00435 INSP-Sprinkler Rough-in/Hydro10/23/200910/23/200910/23/2009 3:16:54 PMPPASS
The underground supply hydro test passed.
BLD09-01864 FIRE-Final Inspection10/23/200910/23/200910/23/2009 3:15:57 PMPFAIL
See the floor plan of the city approved plans for locations and types of deficiencies.
FIR09-00581 INSP-Sprinkler Rough-in/Hydro10/23/200910/23/200910/23/2009 2:05:41 PMPPASS
The underground hydro test passed.
FIR09-00484 INSP-Sprinkler Rough-in/Hydro10/22/200910/23/200910/23/2009 1:47:01 PMAPASS
Rough-in inspection mostly passed. I noted one retaining strap missing, T-bar was not installed and will require a separate inspection and the showroom piping was not accessible for inspection. The hardlid areas are ok for cover.
FIR09-00482 INSP-Sprinkler Rough-in/Hydro10/22/200910/23/200910/23/2009 12:36:43 PMAPASS
The overhead hydro and verification of previous corrections passed. I went over items needed for the final such as fire alarm interconnections, signage at the riser, forward flow verification.....ect.
BLD09-01653 FIRE-Final Inspection10/22/200910/23/200910/23/2009 11:11:53 AMAPASS
Life safety passed. The hood suppression system has been re-certified by Fire Expert.
FIR09-00291 INSP-Sprinkler Rough-in10/22/200910/23/200910/23/2009 10:51:05 AMAPART
Todays inspection was for the coolers and freezers. See the city approved plans for coolers and freezers where piping and pendants where ok. The dairy cooler has fan units causing obstructions to the pendant sprinklers. One arm over requires a hanger above the meat cooler.
BLD09-01272 FIRE-Final Inspection10/22/200910/23/200910/23/2009 10:46:15 AMAPASS
Life safety passed.
FIR09-00435 INSP-Supply line flush10/22/200910/23/200910/23/2009 8:02:39 AMAPASS
The underground flush passed inspection.