FIR12-00378
| FIR-Aging Inspection | 10/23/2012 | 10/23/2012 | 10/30/2012 8:24:02 AM | | DONE |
|
|
No call for inspection.
|
FIR12-00393
| INSP-Final Inspection | 10/23/2012 | 10/23/2012 | 10/23/2012 4:28:06 PM | P | FAIL |
|
|
Overspaced pendent coverage at three classrooms. Previous C/N items dated 10/5 verified for completion.
|
FIR12-00577
| INSP-Final Inspection | 10/23/2012 | 10/23/2012 | 10/23/2012 4:19:32 PM | P | PASS |
|
|
Scope of work completed. Fire sprinkler permit finaled.
|
FIR12-00577
| INSP-Sprinkler Rough-in | 10/23/2012 | 10/23/2012 | 10/23/2012 1:13:41 PM | P | PART |
|
|
Rough-in passed inspection.
|
FIR12-00529
| INSP-Sprinkler Rough-in | 10/22/2012 | 10/23/2012 | 10/23/2012 1:12:19 PM | A | FAIL |
|
|
Noted four pendent heads in need of relocation due to light fixture obstructions, heads at furnace closets to meet temp. ratings per 6.2.3.3.3, verify equipment at the exterior balcony rooms are not fuel-fired.
|
BLD12-01818
| FIRE-Final Inspection | 10/22/2012 | 10/23/2012 | 10/23/2012 12:49:00 PM | A | PASS |
|
|
Fire life safety approved pending correct door hardware is installed at both mezzanine rooms and the fire sprinkler riser room- to be finished prior to structural final as discussed.
|
FIR12-00572
| INSP-Final Inspection | 10/22/2012 | 10/23/2012 | 10/23/2012 12:47:00 PM | A | PASS |
|
|
Correction items verified for completion. Fire sprinkler permit finaled.
|
BLD12-02527
| FIRE-Final Inspection | 10/22/2012 | 10/23/2012 | 10/23/2012 12:45:43 PM | A | FAIL |
|
|
Correction items include hardware at both main entry vestibule doors, repair exit sign, post fire extinguisher per plan.
|