FIR12-00506
| INSP-Final Inspection | 10/22/2012 | 10/23/2012 | 10/23/2012 3:48:49 PM | P | CANC |
|
|
Per Glen inspection is to be rescheduled for tomorrow with the fire alarm inspection.
|
FIR12-00494
| INSP-Sprinkler Rough-in | 10/23/2012 | 10/23/2012 | 10/23/2012 3:39:12 PM | P | PASS |
|
|
ok to cover at the previously marked corrections
|
FIR12-00611
| INSP-Sprinkler Rough-in | 10/23/2012 | 10/23/2012 | 10/23/2012 3:16:57 PM | P | PASS |
|
|
Rough-in inspection passed. Piping can be covered.
|
FIR12-00589
| INSP-Sprinkler Rough-in | 10/22/2012 | 10/23/2012 | 10/23/2012 3:16:14 PM | P | PASS |
|
|
Rough-in inspection passed. Piping can be covered.
|
FIR12-00543
| INSP-Final Inspection | 10/22/2012 | 10/23/2012 | 10/23/2012 3:15:10 PM | A | FAIL |
|
|
Project is not ready for a final inspectio due to the ceiling tile has not been installed. Rough-in inspection has passed and the piping can now be covered.
|
BLD12-02729
| FIRE-Final Inspection | 10/19/2012 | 10/23/2012 | 10/23/2012 11:31:54 AM | A | PASS |
|
|
Life safety passed
|
FIR12-00561
| INSP-Final Inspection | 10/22/2012 | 10/23/2012 | 10/23/2012 11:30:51 AM | A | FAIL |
|
|
The audilbe and visual fire alarm devices shall be syncronized as per NFPA 72, sections 18.4.2.5 and 18.5.4.3.2. (the new devices do not audibly sync with the existing devices) Also corrected as-builts are needed showing the candella changes.
|
BLD12-02695
| FIRE-Final Inspection | 10/22/2012 | 10/23/2012 | 10/23/2012 9:40:06 AM | A | FAIL |
|
|
Provide exit signs/emergency lights as per the approved plans, provide approved single action hardware on all doors as per the approved plans, provide fire extinguishers as discussed.
|
FIR12-00394
| FIR-Aging Inspection | 10/23/2012 | 10/23/2012 | 10/23/2012 8:27:42 AM | | NR |
|
|
Brodie stated he would follow up on the job status.
|