Inspections for the day of: Wednesday, October 23, 2013.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01893 ELE-Aging Inspection10/23/201310/23/201310/25/2013 6:38:59 AM CANC
ELE13-02535 Final10/23/201310/23/201310/23/2013 3:16:03 PMPPART
Randy. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy ok except for furniture, signed t/o card
ELE13-02953 Electrical Rough-In10/23/201310/23/201310/23/2013 2:45:44 PMPPASS
Clyde Phone #: ###-#### ri ok
ELE13-02880 Electrical Rough-In10/23/201310/23/201310/23/2013 2:41:45 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Tim Dunlop ri ok
ELE13-02325 Final10/23/201310/23/201310/23/2013 2:40:11 PMPPASS
ballast and lamp change in office area Phone #: ###-#### >> Inspection requested via web by patrick marks called contractor to explain calling for ri, ok final
ELE13-02930 Permanent Service10/23/201310/23/201310/23/2013 2:11:43 PMPCANC
Greg Phone #: ###-#### see conference
ELE13-02930 Conference10/23/201310/23/201310/23/2013 2:10:25 PMPDONE
Greg Phone #: ###-#### met owner, talked about ground rods, continuous gec, provide service disconnect, wire sub-panel per NEC, gas meter shall not be in front of meter
ELE13-02951 Permanent Service10/23/201310/23/201310/23/2013 2:07:20 PMAFAIL
Service inspection for Idaho Power re-meter. Please call Stuart 1 hr in advance. Phone #: ###-#### >> Inspection requested via web by Stuart Welton met contractor, left correction notice, NEC 408.38 shall provide dead-front, 250.52 shall provide grounding electrodes, 250.64 GEC shall be continuous, 358.30, 348.30 shall strap emt and fmc,BCC shall provide address and labelling
ELE13-02927 Temporary Service10/22/201310/23/201310/23/2013 10:38:36 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Alan Lusk t/s u/g n ok
ELE13-02899 Temporary Service10/22/201310/23/201310/23/2013 10:32:27 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Alan Lusk t/s u/g n ok
ELE13-02897 Temporary Service10/22/201310/23/201310/23/2013 10:13:54 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Alan Lusk t/s u/g n ok
ELE13-02793 Final10/22/201310/23/201310/23/2013 9:52:04 AMAFAIL
Ran conduit for pool and tennis light Phone #: ###-#### >> Inspection requested via web by Neal Rumsey called, shall include pool and tennis court on permit, NEC 300.5 shall bury conduit correct depth, 352.26 shall not be over 360 degree bend in raceway, 300.11 shall not use raceway as means of support
ELE13-02322 Electrical Rough-In10/22/201310/23/201310/23/2013 8:59:03 AMANR
dennis Phone #: ###-#### met owner, talked about 6" free conductor, make-up, add ground rod
ELE13-02938 Electrical Rough-In10/22/201310/23/201310/23/2013 8:33:06 AMAPASS
Must call for access ###-#### unit 108 Phone #: ###-#### >> Inspection requested via web by shane vigil called contractor to change room count to 6 rooms, change address to 108, ri ok
ELE13-02233 Final10/22/201310/23/201310/23/2013 7:56:02 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Randy Fletcher corrections made, p/s o/h rec ok