ELE14-01934
| Electrical Rough-In | 10/23/2014 | 10/23/2014 | 10/23/2014 5:31:46 PM | P | PASS |
|
|
Pole base inspect for 5 locations along franklin side of property. Contact is Justin Bieker. Phone #: ###-#### Inspection requested via web by Richard Montgomery Pole bases only. UG not connected
|
ELE14-02938
| Rough-In Permanent Service | 10/23/2014 | 10/23/2014 | 10/23/2014 4:58:39 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov
300.4 Bored holes, wiring shall be protected from damage 352.10F note: Type sch 80 identified for areas of physical damage
250.148 boxes with multiple circuits, all grounding shall be tied together
|
GCE14-00116
| GCE-Final | 10/23/2014 | 10/23/2014 | 10/23/2014 4:05:39 PM | P | FAIL |
|
|
Daniel ###-#### Corrections not all addreseed, 406.8 Outside receptacles to be of a weather resistant type
|
GCE14-00115
| GCE-Final | 10/23/2014 | 10/23/2014 | 10/23/2014 4:04:23 PM | P | FAIL |
|
|
Daniel 409-269 house open 406.4 Receptacle cover shall be flush with receptacle
314.23.B.1 Nails and screws where used as a fastening, shall be attached by using brackets on the outside of the enclosure
|
ELE14-02961
| Electrical Rough-In | 10/23/2014 | 10/23/2014 | 10/23/2014 2:35:55 PM | P | PART |
|
|
Contact Barry to meet on site Phone #: ###-#### Inspection requested via web by BARRY KENDALL
RI OK to cover demising wall, contractor has a lot of seperating of circuits between two businesses sharing building . To be done in phases. 7 outlets on northern end of wall, seperates warehouse and art studio
|
ELE14-02917
| Final | 10/22/2014 | 10/23/2014 | 10/23/2014 1:59:59 PM | A | CANC |
|
|
Brett Phone #: ###-####
FInal ok
|
ELE14-02916
| Conference | 10/20/2014 | 10/23/2014 | 10/23/2014 1:59:37 PM | A | DONE |
|
|
check for contractor doing work on interior no addtional wiring or circuit extension being done
|
ELE14-02916
| Final | 10/23/2014 | 10/23/2014 | 10/23/2014 1:59:09 PM | P | PASS |
|
|
Service final ok
|
ELE14-02917
| Conference | 10/20/2014 | 10/23/2014 | 10/23/2014 1:57:49 PM | A | DONE |
|
|
check contractor doing work on interior No additional wiring or extension of circuits. Replaceing wall covering only
|
ELE14-02878
| Electrical Rough-In | 10/23/2014 | 10/23/2014 | 10/23/2014 1:56:33 PM | P | PASS |
|
|
Trench inspection from garage to house. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov Trench conduit to garage. OK
|
ELE14-01862
| Final | 10/22/2014 | 10/23/2014 | 10/23/2014 1:34:41 PM | P | PASS |
|
|
Inspector will need to meet Miles there to be let in. Please call ahead to set time. Miles cell ###-#### shop ###-####. Thank you Phone #: ###-#### Inspection requested via web by Sheri Lewis Final OK
|
ELE14-01666
| Final | 10/23/2014 | 10/23/2014 | 10/23/2014 1:16:10 PM | P | PASS |
|
|
Call about the inspection. This may not be ready for the final final. I have a question. Phone #: ###-#### Inspection requested via web by Greg Idsinga Core and shell, Final OK
|
ELE14-02933
| Final | 10/23/2014 | 10/23/2014 | 10/23/2014 1:15:36 PM | P | NR |
|
|
Call about the inspection. Phone #: ###-#### Inspection requested via web by Greg Idsinga Khave Card not on site. Will need to check back
|
ELE14-02934
| Final | 10/23/2014 | 10/23/2014 | 10/23/2014 1:14:41 PM | P | PASS |
|
|
Call about the inspection. Phone #: ###-#### Inspection requested via web by Greg Idsinga Final OK Joyful Tea
|
ELE14-02935
| Final | 10/23/2014 | 10/23/2014 | 10/23/2014 1:14:00 PM | P | NR |
|
|
Call about the inspection. Phone #: ###-#### Inspection requested via web by Greg Idsinga No electrical ready at this time, space not identified
|
MIS14-00210
| ELE-Conference | 10/16/2014 | 10/23/2014 | 10/23/2014 12:39:45 PM | P | DONE |
|
|
Chuck ###-#### check on progress.
No work has been done.
|
ELE14-02409
| Final | 10/23/2014 | 10/23/2014 | 10/23/2014 12:33:11 PM | P | PASS |
|
|
The corrections have been fixed, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen
|
ELE14-02365
| Final | 10/23/2014 | 10/23/2014 | 10/23/2014 12:23:50 PM | P | PASS |
|
|
The corrections have been fixed, any questions please let me know, thx, TW the ACCESS CODE is 6949 (for both homes) Phone #: ###-#### Inspection requested via web by Stephen Kren
|
ELE14-02904
| Conference | 10/17/2014 | 10/23/2014 | 10/23/2014 10:11:29 AM | A | DONE |
|
|
Nancy Phone #: ###-#### Owner looking to add new meters and underground for RV services on personal property
|
ELE14-02675
| Electrical Rough-In | 10/22/2014 | 10/23/2014 | 10/23/2014 9:43:54 AM | A | PASS |
|
|
Site underground cover. Toby is the on site contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
UG as noted on contractor print. RI OK to cover
|
ELE14-02947
| Permanent Service | 10/22/2014 | 10/23/2014 | 10/23/2014 8:56:11 AM | A | FAIL |
|
|
Mter was off for more than 1 year. Lock box on gas meter #4907. Phone #: ###-#### Inspection requested via web by Alan Lusk 352.30 Securing and Supporting. PVC conduit shall be installed as a complete system as provided in 300.18 and shall be fastened so that movement from thermal expansion or contraction is permitted. PVC conduit shall be securely fastened and supported in accordance with 352.30(A) and (B). (A) Securely Fastened. PVC conduit shall be securely fastened within 900 mm (3 ft) of each outlet box, junction box, device box, conduit body, or other conduit termination. Conduit listed for securing at other than 900 mm (3 ft) shall be permitted to be installed in accordance with the listing. 110.12.B (B) Integrity of Electrical Equipment and Connections. Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, shall not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues. There shall be no damaged parts that may adversely affect safe operation or mechanical strength of the equipment such as parts that are broken; bent; cut; or deteriorated by corrosion, chemical action, or overheating.
110.26.a.1 Working spaces shall be maintained. 3 ft. clearance. Remove tomato plant.
|
ELE14-02947
| Permanent Service | 10/22/2014 | 10/23/2014 | 10/22/2014 9:58:42 AM | A | CANC |
|
|
Service was off more than 1 year Phone #: ###-#### >> Inspection requested via web by Alan Lusk Inspection cancelled from web by: Alan Lusk
|