Inspections for the day of: Monday, October 23, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03557 Conference10/23/201710/23/201710/23/2017 3:25:45 PMPDONE
Mitch Phone #: ###-####
4-05-32 Code violations not to be retained.
4-05-31(C)- Unfused conductors shall not enter a building unless considered outside building as defined in NEC 230.6.
NEC 230.70- A service disconnecting means shall be provided for each service, 1 single phase and 1 3 phase with high leg enters through roof and terminates in panel boards on interior of building. Required labels and high leg marking.
ELE17-02678 Final10/23/201710/23/201710/23/2017 2:26:51 PMPPASS
Terry Cushing is contact at ###-####. Phone #: ###-#### Inspection requested via web by Debby Pierce
Final ok
ELE17-02791 Electrical Rough-In10/23/201710/23/201710/23/2017 1:58:18 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Grid rough in ok cover
ELE17-03191 Electrical Rough-In10/19/201710/23/201710/23/2017 1:11:57 PMPPASS
Call Bryce if any questions Phone #: ###-#### Inspection requested via web by Christian Kilpatrick
Listing confirmed rough in ok
ELE17-03190 Rough-In Permanent Service10/19/201710/23/201710/23/2017 1:08:50 PMPNR
Call Bryce if any questions Phone #: ###-#### Inspection requested via web by Christian Kilpatrick
Unable to schedule Idaho power to disconnect until 10/24. Will recall. Discussed required grounding electrode system, verify all existing to determine.
ELE17-03449 Final10/20/201710/23/201710/23/2017 9:55:16 AMAPASS
Inspection requested via web by Thomas wilson Final ok
ELE17-03495 Final10/20/201710/23/201710/23/2017 9:45:23 AMAPASS
Inspection requested via web by Thomas wilson Final ok
ELE17-03495 Final10/20/201710/23/201710/23/2017 9:41:26 AMAPASS
Inspection requested via web by Thomas wilson Final ok
ELE17-02111 Final10/20/201710/23/201710/23/2017 9:14:29 AMAPASS
Phone #: ###-#### Inspection requested via web by Rowdy Monroe
Final ok
ELE17-01884 Final10/20/201710/23/201710/23/2017 7:52:45 AMAPASS
Install 2 sets of letters reading The Wylder and 1 small blade sign. All Primary power by others Phone #: ###-#### Inspection requested via web by Ken Olsen Final ok