Inspections for the day of: Monday, October 23, 2017.
Number of inspections: 3
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-03847 FIRE-Final Inspection10/23/201710/23/201710/23/2017 12:21:39 PMAPASS
Life fire safety inspection completed on 04OCT2017 for vanilla finish TI
FIR17-00178 INSP-Conference10/23/201710/23/201710/23/2017 10:37:00 AMPDONE
Discuss requirements for passenger elevator control room/and shaft.
Currently the elevator controller is in the shaft space. There are no walls or hard lid that separate the controller and the shaft. Top of the shaft is 60ft above controller. Device maintenance is a concern.
Tribal Fire also questions the location of the sprinkler heads needed.


Issue is deferred to fire alarm system design and plan review to provide a solution.
FIR17-00267 INSP-Sprinkler Rough-in10/20/201710/23/201710/23/2017 9:54:46 AMAPART
Rough to cover inspection for overhead fire sprinkler piping located above the sheetrock in corridors (corridors only), east side of elevator lobby on levels 2 and 3 complete, approved for cover.