Inspections for the day of: Wednesday, October 23, 2019.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03356 Permanent Service10/23/201910/23/201910/23/2019 2:33:52 PMPPASS
Phone #: ###-#### Inspection requested via web by jamie berg p/s u/g rec ok
ELE19-03357 Permanent Service10/23/201910/23/201910/23/2019 2:13:48 PMPPASS
Phone #: ###-#### Inspection requested via web by jamie berg p/s u/g rec ok
ELE19-02678 Permanent Service10/23/201910/23/201910/23/2019 2:13:21 PMPPASS
Phone #: ###-#### Inspection requested via web by jamie berg p/s u/g rec ok
ELE19-03752 Electrical Rough-In10/22/201910/23/201910/23/2019 2:10:07 PMPPART
Underground conduit inspection
Contact Steve Hess
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Both ends of trench will be left open for inspection of 4/0 connection to ground rings of building and tower pad. OK to cover between generator pad and tower pad only.
ELE19-03162 Final10/23/201910/23/201910/23/2019 1:40:23 PMPPASS
Phone #: ###-#### Inspection requested via web by jamie berg final ok
ELE19-02924 Final10/23/201910/23/201910/23/2019 1:25:26 PMPPASS
Phone #: ###-#### Inspection requested via web by Robert Murray final ok
ELE19-02683 Final10/23/201910/23/201910/23/2019 1:25:09 PMPPASS
Phone #: ###-#### Inspection requested via web by Robert Murray final ok
ELE19-01582 Electrical Rough-In10/22/201910/23/201910/23/2019 12:57:51 PMPPASS
Underground Inspection, Shannon is the contact Phone #: ###-#### Inspection requested via web by Deb Ipsen Underground to entry sign only ok to cover
ELE19-02648 Final10/23/201910/23/201910/23/2019 12:29:11 PMPFAIL
Phone #: ###-#### Inspection requested via web by Tom Jenkins 210.8 receps within 6ft of sink shall be GFCI protected. (Janitor closet) 210.62 Show room receps required. (Marked on print to stay) 422.30 Disc. shall be readily accessible ( Water heater disc is located on ceiling)
ELE19-03593 Electrical Rough-In10/23/201910/23/201910/23/2019 11:26:24 AMAPASS
Colton Phone #: ###-#### listing only ok
ELE19-03976 Rough-In Permanent Service10/22/201910/23/201910/23/2019 11:13:01 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn House was foam sealed at time of rough in. Rough in ok p/s u/g n ok
ELE19-03522 Final10/22/201910/23/201910/23/2019 10:30:26 AMAPASS
contact lance with questions
208.703.2035 Phone #: ###-#### Inspection requested via web by David Feller final ok
ELE19-00910 Final10/22/201910/23/201910/23/2019 10:12:06 AMAPASS
Contact Brandon for finalizing any remaining open issues. (GFCI protection) Phone #: ###-#### Inspection requested via web by Tom Betty All items have been corrected final ok
ELE19-02945 Final10/22/201910/23/201910/23/2019 9:29:35 AMAPASS
contact Lance with any questions
208.703.2035 Phone #: ###-#### Inspection requested via web by David Feller final ok
ELE19-03316 Final10/18/201910/23/201910/23/2019 8:47:51 AMAPASS
Homeowner has plans and permit with her. Phone #: ###-#### Inspection requested via web by Ashley Lanham Final ok
ELE19-03593 Electrical Rough-In10/22/201910/23/201910/23/2019 8:47:08 AMACANC
Colton Phone #: ###-####