FIR05-00076
| INSP-Alarm Testing | 10/24/2005 | 10/24/2005 | 10/24/2005 4:45:45 PM | A | PART |
|
|
Partial shell alarm inspection only.
|
FIR05-00075
| INSP-Alarm Testing | 10/24/2005 | 10/24/2005 | 10/24/2005 4:44:24 PM | A | FAIL |
|
|
Need to retest elevator lobby smoke detectors as they have been connected and reconnected for ceiling tile installation, need to test elevator heat detector in pit, provide sign at FACP room, no knox box provided yet, need audibility in the FACP room as discussed.
|
FIR05-00426
| INSP-Alarm Testing | 10/24/2005 | 10/24/2005 | 10/24/2005 4:36:21 PM | A | FAIL |
|
|
Provide resubmittals for changes( added strobe, 180cd strobes at outside seating area, moved 75cd strobe in the kitchen) some duct smoke detectors are mounted incorrectly.
|
FIR05-00459
| INSP-Alarm Testing | 10/24/2005 | 10/24/2005 | 10/24/2005 4:32:07 PM | P | CANC |
|
|
No time available for this inspection today.
|
FIR05-00559
| INSP-Final Inspection | 10/21/2005 | 10/24/2005 | 10/24/2005 4:30:52 PM | P | FAIL |
|
|
Orientation and length of the sample tubes in the ductwork are not correctly installed, activation of the duct smoke detector produced a weak intermittent alarm signal reading 4.5 at the EOL under battery power.
|
BLD05-01993
| FIRE-Final Inspection | 10/24/2005 | 10/24/2005 | 10/24/2005 3:36:29 PM | P | CANC |
|
|
No time available for this inspection today, spoke with contractor to reschedule for tomorrow am.
|
BLD05-02218
| BLD-Framing/Rough-in | 10/21/2005 | 10/24/2005 | 10/24/2005 3:33:33 PM | A | CANC |
|
|
Wrong inspection type called in, notified contractor at ###-####.
|
BLD04-01323
| FIRE-Final Inspection | 10/21/2005 | 10/24/2005 | 10/24/2005 3:08:39 PM | P | FAIL |
|
|
A 12 item correction list was discussed and left with Gary of Devcon construction for the shell permit life safety.
|
FIR05-00089
| INSP-Sprinkler Rough-in/Hydro | 10/21/2005 | 10/24/2005 | 10/24/2005 3:06:31 PM | A | FAIL |
|
|
A 13 item correction list was discussed and left with Brian of DeBest sprinkler for the shell rough-in.
|
FIR05-00520
| INSP-Final Inspection | 10/24/2005 | 10/24/2005 | 10/24/2005 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 10/24/2005 at 7:58:44 AM. Contact: ###-####. canc kirk
|
FIR05-00531
| INSP-Alarm Testing | 10/24/2005 | 10/24/2005 | 10/24/2005 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 10/24/2005 at 8:01:03 AM. Contact: ###-####. cancel
|