Inspections for the day of: Monday, October 24, 2005.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00586 FIR-Aging Inspection10/24/200510/24/200510/31/2005 2:38:03 PM PASS
permit finaled
FIR03-00711 FIR-Aging Inspection10/24/200510/24/200510/28/2005 2:22:37 PM FAIL
I left notice with the blonde bartender that the hood will be redtagged for shutdown next friday if the corrections don't happen.
FIR03-00524 FIR-Aging Inspection10/24/200510/24/200510/27/2005 1:19:50 PM NR
I spoke to Joe and told him I would give him until the end of next week to get this permit finaled or I would red tag the hood.
BLD05-01543 FIRE-Final Inspection10/24/200510/24/200510/25/2005 9:59:28 AMPPASS
Life safety finaled
FIR05-00492 INSP-Final Inspection10/24/200510/24/200510/25/2005 9:58:16 AMPPASS
Permit finaled
FIR05-00652 INSP-Final Inspection10/24/200510/24/200510/24/2005 4:51:03 PMPFAIL
Sprinkler piping in the office area is ok to cover but there are two existing upright sprinklers in the warehouse area that are located under the skylights/smoke vents. Per the superintendant they are drop out sky lights. The upright heads will need to be relocated but shall not exceed the 196 sq. ft. spacing.
BLD05-00327 FIRE-Final Inspection10/21/200510/24/200510/24/2005 4:49:02 PMPPASS
Fire life safety finaled
BLD05-01979 FIRE-Final Inspection10/24/200510/24/200510/24/2005 4:48:38 PMPPASS
Fire life safety finaled
BLD05-02844 FIRE-Final Inspection10/24/200510/24/200510/24/2005 4:47:42 PMPPASS
Life safety finaled
FIR05-00360 INSP-Final Inspection10/24/200510/24/200510/24/2005 11:53:01 AMPPASS
Fire sprinklers finaled
FIR05-00492 INSP-Final Inspection10/21/200510/24/200510/24/2005 11:41:56 AMAFAIL
All devices have been tested and operate ok but the signals are incorrect at the monitoring station.
BLD05-01543 FIRE-Final Inspection10/21/200510/24/200510/24/2005 11:41:04 AMAFAIL
Fire alarm permit needs finaling. Life safety is ok to final when this is done.
FIR05-00257 INSP-Alarm Testing10/21/200510/24/200510/24/2005 11:39:15 AMAFAIL
Non of the induct detectors operated, probably due to the airflow in ducts. They will need to be tested later. See city approved resubmitted plans for the ceiling mounted detectors and strobes that have been inspected.
FIR05-00645 INSP-Final Inspection10/21/200510/24/200510/24/2005 11:03:39 AMPCANC
Troy, Please let us know what time wil work for you. My cell is ###-####. Office is ###-####. Thanks, Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick Inspection cancelled from web by: Jason Minnick