Inspections for the day of: Tuesday, October 24, 2006.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03164 Permanent Service10/24/200610/24/200610/24/2006 3:49:04 PMPFAIL
rhonda; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
corr. called 314.28 (A)(2) needs 6 times the diameter between entries 21/2" conduit, at jbox below new panel needs 15", also label meter space
ELE06-03925 Electrical Rough-In10/24/200610/24/200610/24/2006 2:49:25 PMPFAIL
Dave; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
corr. called 314.16 box fill 2 gang new back bed rm, 314.17 (C) cable sheath shall enter into boxes 1/4" afci for both new bed rms, new back bed rm on small appliance branch circuit ? called
ELE06-03231 Permanent Service10/24/200610/24/200610/24/2006 2:21:43 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs corr needs bonding at p/s , needs 4/0 or 200 amp main breaker, bond water system when installed
ELE06-03351 Rough-In Permanent Service10/23/200610/24/200610/24/2006 1:50:18 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i all 4 units
p/s u/g new ok
ELE06-03350 Rough-In Permanent Service10/23/200610/24/200610/24/2006 1:48:48 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i all 4 units, p/s u/g new ok
ELE06-03921 Temporary Service10/23/200610/24/200610/24/2006 12:06:48 PMAFAIL
Phone #: ###-#### Internet Inspection Request from: Nikki Day needs 60 amp max to job trailer, tie bar for 2 pole 60 amp breaker and complete wiring at t/s called
ELE06-03441 Electrical Rough-In10/23/200610/24/200610/24/2006 11:17:53 AMAPART
CEILING COVER - CONTACT BUSTER BOWEN ; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok
ELE06-03895 Final10/20/200610/24/200610/24/2006 10:58:32 AMAPASS
###-#### mike no card ok
ELE06-03906 Electrical Rough-In10/23/200610/24/200610/24/2006 10:26:14 AMAPART
Steve; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
u/g around fountain
ELE06-03907 Final10/23/200610/24/200610/24/2006 10:04:14 AMAFAIL
Business opens at 9am. thanks. Randy ###-####; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher corr. called 210.8(B) gfci all 120 V recepts in counter area, 250.122 shall grd
boxes and install #10 for 30 amp circuit, 110.b needs GE breakers, check box fill 4sq below panel, and derate conductors 3/4 emt
ELE06-03795 Electrical Rough-In10/23/200610/24/200610/23/2006 1:01:09 PMACANC
PLEASE INSPECT THE UNDERGROUND FOR THE NEW PARKING LOT LIGHTING. THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH Inspection cancelled from web by: BRIAN KEITH