ELE06-03164
| Permanent Service | 10/24/2006 | 10/24/2006 | 10/24/2006 3:49:04 PM | P | FAIL |
|
|
rhonda; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr. called 314.28 (A)(2) needs 6 times the diameter between entries 21/2" conduit, at jbox below new panel needs 15", also label meter space
|
ELE06-03925
| Electrical Rough-In | 10/24/2006 | 10/24/2006 | 10/24/2006 2:49:25 PM | P | FAIL |
|
|
Dave; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt corr. called 314.16 box fill 2 gang new back bed rm, 314.17 (C) cable sheath shall enter into boxes 1/4" afci for both new bed rms, new back bed rm on small appliance branch circuit ? called
|
ELE06-03231
| Permanent Service | 10/24/2006 | 10/24/2006 | 10/24/2006 2:21:43 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs corr needs bonding at p/s , needs 4/0 or 200 amp main breaker, bond water system when installed
|
ELE06-03351
| Rough-In Permanent Service | 10/23/2006 | 10/24/2006 | 10/24/2006 1:50:18 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i all 4 units p/s u/g new ok
|
ELE06-03350
| Rough-In Permanent Service | 10/23/2006 | 10/24/2006 | 10/24/2006 1:48:48 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson r/i all 4 units, p/s u/g new ok
|
ELE06-03921
| Temporary Service | 10/23/2006 | 10/24/2006 | 10/24/2006 12:06:48 PM | A | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Nikki Day needs 60 amp max to job trailer, tie bar for 2 pole 60 amp breaker and complete wiring at t/s called
|
ELE06-03441
| Electrical Rough-In | 10/23/2006 | 10/24/2006 | 10/24/2006 11:17:53 AM | A | PART |
|
|
CEILING COVER - CONTACT BUSTER BOWEN ; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok
|
ELE06-03895
| Final | 10/20/2006 | 10/24/2006 | 10/24/2006 10:58:32 AM | A | PASS |
|
|
###-#### mike no card ok
|
ELE06-03906
| Electrical Rough-In | 10/23/2006 | 10/24/2006 | 10/24/2006 10:26:14 AM | A | PART |
|
|
Steve; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt u/g around fountain
|
ELE06-03907
| Final | 10/23/2006 | 10/24/2006 | 10/24/2006 10:04:14 AM | A | FAIL |
|
|
Business opens at 9am. thanks. Randy ###-####; Phone #: ###-#### Internet Inspection Request from: Randy Fletcher corr. called 210.8(B) gfci all 120 V recepts in counter area, 250.122 shall grd boxes and install #10 for 30 amp circuit, 110.b needs GE breakers, check box fill 4sq below panel, and derate conductors 3/4 emt
|
ELE06-03795
| Electrical Rough-In | 10/23/2006 | 10/24/2006 | 10/23/2006 1:01:09 PM | A | CANC |
|
|
PLEASE INSPECT THE UNDERGROUND FOR THE NEW PARKING LOT LIGHTING. THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH Inspection cancelled from web by: BRIAN KEITH
|