Inspections for the day of: Tuesday, October 24, 2006.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMike Kinnear
TitleELE-INSPECTOR
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-04616 Final10/23/200610/24/200610/24/2006 4:39:52 PMPFAIL
MORGAN CALL PRIOR TO HEADING TO SITE. LATE AFTERNOON; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy corrections nec410.30(1) 1 the fixture shall be located directly below the outlet. (upstairs light fixtures) boise city code 4-05-33(A) all electrical equipment shall be listed & so labled by an approved testing laboratory. ( downstairs hoists) note unabled to inspect the whole building owner moved in.
ELE06-01543 Electrical Rough-In10/23/200610/24/200610/24/2006 4:34:05 PMPFAIL
CONTACT: MARSHALL DOBSON - CEILING ROUGH IN; Phone #: ###-#### Internet Inspection Request from: Deb McCoy boise city code no ceiling shall be installed that is not related to electrical reinspection fee
ELE06-01543 Electrical Rough-In10/24/200610/24/200610/24/2006 4:32:32 PMPFAIL
CONTACT: MARSHALL DOBSON - CEILING ROUGH IN; Phone #: ###-#### Internet Inspection Request from: Deb McCoy boise city code no ceiling tile shall be installed that is not related to electrical reinspection fee
ELE06-01277 Electrical Rough-In10/24/200610/24/200610/24/2006 4:26:33 PMAPART
ok connection to machinery near panel note not all the equipment has been moved into building yet
ELE06-03913 Permanent Service10/23/200610/24/200610/24/2006 1:06:10 PMAPASS
building 5; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie p/s u/g n ok
ELE06-03452 Electrical Rough-In10/23/200610/24/200610/24/2006 1:05:45 PMAPASS
building 4; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok cover west 1/2 of building only
ELE06-01277 Final10/23/200610/24/200610/24/2006 12:10:35 PMACANC
Please call 30 minutes ahead as there is no one on site. Thank you.; Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton wrong type inspection
ELE06-03746 Electrical Rough-In10/23/200610/24/200610/24/2006 12:08:36 PMAPART
dennis ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok cover walls only
ELE06-02743 ELE-Aging Inspection10/24/200610/24/200610/24/2006 11:38:27 AM PASS
ok final 2 wall signs
ELE06-02743 Final10/24/200610/24/200610/24/2006 11:37:58 AMPPASS
ok final 2 wall signs
ELE06-02872 Final10/23/200610/24/200610/24/2006 11:35:34 AMAPASS
alan; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok final
ELE06-03657 Final10/23/200610/24/200610/24/2006 11:12:10 AMAFAIL
Charles; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt nec210.52 (A) sunroom shall have receptacles 6ft from openings & not more than 12ft apart
ELE06-03510 Electrical Rough-In10/23/200610/24/200610/24/2006 10:36:01 AMAPASS
Steven ###-#### ok cover ri
ELE06-03806 Electrical Rough-In10/23/200610/24/200610/24/2006 10:15:34 AMAFAIL
james ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie nec300.4(D) through out the house
ELE06-03806 Permanent Service10/24/200610/24/200610/24/2006 10:14:35 AMPPASS
james ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie p/s u/g n ok
ELE06-03891 Final10/23/200610/24/200610/24/2006 9:53:05 AMACANC
mike - note: re-inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith wrong type inspection
ELE06-03891 Electrical Rough-In10/24/200610/24/200610/24/2006 9:52:01 AMPPASS
mike - note: re-inspection ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok cover ri correction made
ELE06-02789 Final10/23/200610/24/200610/24/2006 9:51:21 AMANR
mike; Phone #: ###-#### Internet Inspection Request from: Patricia Smith job not ready called mike
ELE06-03831 Permanent Service10/23/200610/24/200610/24/2006 9:05:04 AMAFAIL
phil; Phone #: ###-#### Internet Inspection Request from: Patricia Smith 2 ground rods & grounded & grounding conductors terminate together on same bus bar
ELE06-02786 Permanent Service10/23/200610/24/200610/24/2006 8:42:56 AMAPASS
kyle; Phone #: ###-#### Internet Inspection Request from: Patricia Smith p/s o/h reconnect ok
ELE06-02740 ELE-Aging Inspection10/24/200610/24/200610/24/2006 6:52:01 AM NR
suc