FIR11-00554
| INSP-Sprinkler Rough-in | 10/24/2011 | 10/24/2011 | 10/24/2011 4:52:59 PM | P | PART |
|
|
Overhead work approved for cover at the drop ceiling as marked and dated on stamped plan set.
|
FIR11-00443
| INSP-Conference | 10/24/2011 | 10/24/2011 | 10/24/2011 4:51:36 PM | P | DONE |
|
|
Conversation with contractor regarding notification appliance locations at the remodel area.
|
FIR11-00210
| INSP-Final Inspection | 10/24/2011 | 10/24/2011 | 10/24/2011 4:49:20 PM | P | PASS |
|
|
Scope of fire sprinkler permit work okay for final.
|
FIR11-00210
| INSP-Sprinkler Rough-in | 10/24/2011 | 10/24/2011 | 10/24/2011 4:45:18 PM | P | PART |
|
|
Fire sprinkler install okayed for cover.
|
FIR09-00059
| FIR-Aging Inspection | 10/24/2011 | 10/24/2011 | 10/24/2011 2:38:15 PM | | DONE |
|
|
|
FIR03-00411
| FIR-Aging Inspection | 10/24/2011 | 10/24/2011 | 10/24/2011 2:37:59 PM | | DONE |
|
|
|
BLD11-02182
| FIRE-Final Inspection | 10/21/2011 | 10/24/2011 | 10/24/2011 2:34:03 PM | A | PASS |
|
|
Correction notice items verified for completion. Life safety passed.
|
BLD11-02463
| FIRE-Final Inspection | 10/17/2011 | 10/24/2011 | 10/24/2011 2:33:00 PM | A | FAIL |
|
|
Fire extinguishers at the retail store and fuel islands are overdue annual certification. Remainder of inspection items passed.
|
FIR10-00606
| FIR-Aging Inspection | 10/24/2011 | 10/24/2011 | 10/24/2011 2:31:31 PM | A | DONE |
|
|
Conversation with tenant rep. regarding items for permit final.
|
BLD11-02487
| FIRE-Final Inspection | 10/17/2011 | 10/24/2011 | 10/24/2011 2:29:53 PM | A | FAIL |
|
|
See items # 2 and 4 on the permit documents list of general requirements. Items include door hardware at the main entry/exit and one missing fire extinguisher.
|