Inspections for the day of: Thursday, October 24, 2013.
Number of inspections: 21
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00001 FIR-Aging Inspection10/24/201310/24/201310/29/2013 9:31:15 AM NR
I left voice message for Dave requesting a follow up on the job status.
BLD13-02883 FIRE-Final Inspection10/24/201310/24/201310/24/2013 5:11:03 PMPCANC
Overbooked but Chris and I discussed general life safety requirements on the phone. Per Chris the phone lines for the fire alarm system are being re-installed. I told him that I would need "certification" that the monitoring had been set up and the system tested prior to a final inspection.
BLD12-03121 FIRE-Final Inspection10/23/201310/24/201310/24/2013 5:08:05 PMPPART
A temporary occupancy is being given until the fire dept approves the height of the islands
BLD13-01052 FIRE-Final Inspection10/24/201310/24/201310/24/2013 5:05:42 PMPCANC
Overbooked. Rescheduled for tomorrow
BLD13-01918 FIRE-Final Inspection10/23/201310/24/201310/24/2013 4:28:33 PMPFAIL
Strobe still has not been corrected yet.
FIR13-00275 INSP-Final Inspection10/24/201310/24/201310/24/2013 3:58:10 PMPCANC
Overbooked. Rescheduled for tomorrow
FIR06-00798 INSP-Final Inspection10/21/201310/24/201310/24/2013 3:57:13 PMACANC
Overbooked. Per conversation with Jason this will be rescheduled for tomorrow.
FIR13-00506 INSP-Sprinkler Rough-in10/24/201310/24/201310/24/2013 3:53:13 PMPPASS
sprinkler piping is ok to cover
BLD13-02718 FIRE-Final Inspection10/24/201310/24/201310/24/2013 2:47:45 PMPPASS
life safety passed. Provide sticker, as discussed, at the main exit prior to the building inspection
FIR13-00379 INSP-Sprinkler Rough-in10/24/201310/24/201310/24/2013 2:06:35 PMPPART
Pendant heads are overspaced in three of the below mezzanine offices. Final spacing will be verified at the final inspection. The rough-in passed for the lobby piping (need two branchline restraints) and the second floor piping.
FIR13-00362 INSP-Sprinkler Rough-in10/24/201310/24/201310/24/2013 2:04:54 PMPPART
Pendant sprinkler heads are overspaced in three of the below mezzanine offices. Piping can be covered and the spacing will be verified at the final inspection. Sprinkler rough-in passed in the lobby area and the second floor area.
FIR13-00273 INSP-Supply line flush10/24/201310/24/201310/24/2013 2:02:39 PMPPASS
Underground tie-ins on both sides of the building are ok to cover and the underground flush passed.
FIR13-00441 INSP-Sprinkler Rough-in/Hydro10/24/201310/24/201310/24/2013 1:57:45 PMPPASS
Above ground hydro passed
FIR13-00342 INSP-Sprinkler Rough-in/Hydro10/24/201310/24/201310/24/2013 1:55:11 PMPPASS
Overhead hydro passed
BLD13-02910 FIRE-Final Inspection10/23/201310/24/201310/24/2013 12:02:17 PMACANC
I left two voice messages for Herb but did not receive a reply. Building inspector said he would verify my items if he could contact tenant. phone #: ###-####
FIR13-00529 INSP-Sprinkler Rough-in10/23/201310/24/201310/24/2013 11:25:38 AMAPASS
Sprinkler piping is ok to cover.
BLD13-00729 FIRE-Final Inspection10/24/201310/24/201310/24/2013 9:42:28 AMPPASS
Life safety passed
FIR13-00248 INSP-Final Inspection10/23/201310/24/201310/24/2013 9:41:03 AMAPASS
Permit finaled
FIR13-00264 INSP-Sprinkler Rough-in/Hydro10/24/201310/24/201310/24/2013 9:38:03 AMAPART
Dry system air test started at 9:30 with 44psi on the guage.
FIR13-00386 INSP-Sprinkler Rough-in10/23/201310/24/201310/24/2013 8:42:36 AMAPASS
Piping is ok to cover.
FIR13-00498 INSP-Final Inspection10/23/201310/24/201310/24/2013 7:57:34 AMAFAIL
Missing the "request to exit" button at the Print Shop/Stair exterior exit door.