ELE10-02067
| ELE-Aging Inspection | 10/24/2014 | 10/24/2014 | 10/27/2014 2:56:31 PM | | DONE |
|
|
Waiting on UL verification
|
ELE12-01528
| ELE-Aging Inspection | 10/24/2014 | 10/24/2014 | 10/27/2014 2:16:11 PM | | DONE |
|
|
Waiting on contractor to check on job
|
ELE12-02081
| ELE-Aging Inspection | 10/24/2014 | 10/24/2014 | 10/27/2014 1:44:29 PM | | DONE |
|
|
Waiting on owner
|
ELE14-02973
| Rough-In Permanent Service | 10/24/2014 | 10/24/2014 | 10/24/2014 3:02:29 PM | P | PASS |
|
|
Late in day if possible. Need ok for Idaho power to restore power to home Phone #: ###-#### Inspection requested via web by Randy Fletcher
Permanent service only. OK PS, OH, RC, OK
|
ELE14-02974
| Final | 10/24/2014 | 10/24/2014 | 10/24/2014 2:37:50 PM | P | FAIL |
|
|
call prior to arrival for access. Phone #: ###-#### Inspection requested via web by Patrick Paz
408.4 Every circuit shall be identified as to its purpose 250.110 Equipment grounds loose in panel
|
ELE14-02974
| Permanent Service | 10/24/2014 | 10/24/2014 | 10/24/2014 2:37:13 PM | P | PASS |
|
|
call prior to arrival for access. Phone #: ###-#### Inspection requested via web by Patrick Paz
PS ,OH, RC OK
|
ELE14-02922
| Electrical Rough-In | 10/22/2014 | 10/24/2014 | 10/24/2014 12:47:52 PM | P | PASS |
|
|
trench insp // Bryant Phone #: ###-####
Trench OK
|
ELE14-02972
| Final | 10/24/2014 | 10/24/2014 | 10/24/2014 12:34:45 PM | P | CANC |
|
|
SPACE # 5 Phone #: ###-#### Inspection requested via web by Dan Rohl
|
ELE14-02972
| Permanent Service | 10/24/2014 | 10/24/2014 | 10/24/2014 12:34:35 PM | P | FAIL |
|
|
SPACE # 5 Phone #: ###-#### Inspection requested via web by Dan Rohl
4.05.32 Code violations not to be retained 250.53(a)(2) Supplemental electrode (ground rod) required 2 per service 314.23(A) Enclosures shall be rigidly and securly fastened in place 250.94(B) Method of Bonding at the Service. Bonding jumpers meeting the requirements of this article shall be used around impaired connections, such as reducing washers or oversized, concentric, or eccentric knockouts. Standard locknuts or bushings shall not be the only means for the bonding required by this section but shall be permitted to be installed to make a mechanical connection of the raceway(s). Electrical continuity at service equipment, service raceways, and service conductor enclosures shall be ensured by one of the following methods: (1) Bonding equipment to the grounded service conductor in a manner provided in 250.8 (2) Connections utilizing threaded couplings or threaded hubs on enclosures if made up wrenchtight (3) Threadless couplings and connectors if made up tight for metal raceways and metal-clad cables (4) Other listed devices, such as bonding-type locknuts, bushings, or bushings with bonding jumpers 230.70 Marking. Each service disconnect shall be permanently marked as to its purpose
|
ELE14-02971
| Permanent Service | 10/24/2014 | 10/24/2014 | 10/24/2014 12:33:26 PM | P | FAIL |
|
|
SPACE # 4 Phone #: ###-#### Inspection requested via web by Dan Rohl
4.05.32 Code violations not to be retained 250.53(a)(2) Supplemental electrode (ground rod) required 2 per service 314.23(A) Enclosures shall be rigidly and securly fastened in place 250.94(B) Method of Bonding at the Service. Bonding jumpers meeting the requirements of this article shall be used around impaired connections, such as reducing washers or oversized, concentric, or eccentric knockouts. Standard locknuts or bushings shall not be the only means for the bonding required by this section but shall be permitted to be installed to make a mechanical connection of the raceway(s). Electrical continuity at service equipment, service raceways, and service conductor enclosures shall be ensured by one of the following methods: (1) Bonding equipment to the grounded service conductor in a manner provided in 250.8 (2) Connections utilizing threaded couplings or threaded hubs on enclosures if made up wrenchtight (3) Threadless couplings and connectors if made up tight for metal raceways and metal-clad cables (4) Other listed devices, such as bonding-type locknuts, bushings, or bushings with bonding jumpers 230.70 Marking. Each service disconnect shall be permanently marked as to its purpose
|
ELE14-02970
| Permanent Service | 10/24/2014 | 10/24/2014 | 10/24/2014 12:32:45 PM | P | FAIL |
|
|
SPACE #1 Phone #: ###-#### Inspection requested via web by Dan Rohl 4.05.32 Code violations not to be retained 250.53(a)(2) Supplemental electrode (ground rod) required 2 per service 314.23(A) Enclosures shall be rigidly and securly fastened in place 250.94(B) Method of Bonding at the Service. Bonding jumpers meeting the requirements of this article shall be used around impaired connections, such as reducing washers or oversized, concentric, or eccentric knockouts. Standard locknuts or bushings shall not be the only means for the bonding required by this section but shall be permitted to be installed to make a mechanical connection of the raceway(s). Electrical continuity at service equipment, service raceways, and service conductor enclosures shall be ensured by one of the following methods: (1) Bonding equipment to the grounded service conductor in a manner provided in 250.8 (2) Connections utilizing threaded couplings or threaded hubs on enclosures if made up wrenchtight (3) Threadless couplings and connectors if made up tight for metal raceways and metal-clad cables (4) Other listed devices, such as bonding-type locknuts, bushings, or bushings with bonding jumpers 230.70 Marking. Each service disconnect shall be permanently marked as to its purpose
|
ELE14-02871
| Final | 10/23/2014 | 10/24/2014 | 10/24/2014 11:10:40 AM | P | CANC |
|
|
panel schedule and lock out done. Thanks Phone #: ###-#### Inspection requested via web by Rick Beckman FInal OK
|
ELE14-02962
| Final | 10/23/2014 | 10/24/2014 | 10/24/2014 10:27:58 AM | A | PASS |
|
|
Final connections for coolers and freezers in front of store, and walk in cooler and walk in freezer in back of store. Phone #: ###-#### Inspection requested via web by Andy Rose
Freezers and coolers OK
|
ELE14-02870
| Electrical Rough-In | 10/23/2014 | 10/24/2014 | 10/24/2014 9:59:57 AM | A | PASS |
|
|
walls and ceilings for cover also look at service to see if ok like we did it call steve with questions Phone #: ###-#### Inspection requested via web by Don Lustig
Wall cover OK
|
ELE14-02960
| Rough-In Permanent Service | 10/23/2014 | 10/24/2014 | 10/24/2014 9:10:26 AM | A | FAIL |
|
|
Rough and Service inspection Inspection requested via web by Rowdy Monroe 300.13(B) Device Removal. In multiwire branch circuits, the continuity of a grounded conductor shall not depend on device connections such as lampholders, receptacles, and so forth, where the removal of such devices would interrupt the continuity.
|
ELE14-02965
| Conference | 10/23/2014 | 10/24/2014 | 10/23/2014 12:00:00 AM | A | DONE |
|
|
Josh Phone #: ###-####-would like as early as possilbe and can you please call with a meet time?
|