Inspections for the day of: Friday, October 24, 2014.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-02067 ELE-Aging Inspection10/24/201410/24/201410/27/2014 2:56:31 PM DONE
Waiting on UL verification
ELE12-01528 ELE-Aging Inspection10/24/201410/24/201410/27/2014 2:16:11 PM DONE
Waiting on contractor to check on job
ELE12-02081 ELE-Aging Inspection10/24/201410/24/201410/27/2014 1:44:29 PM DONE
Waiting on owner
ELE14-02973 Rough-In Permanent Service10/24/201410/24/201410/24/2014 3:02:29 PMPPASS
Late in day if possible. Need ok for Idaho power to restore power to home Phone #: ###-#### Inspection requested via web by Randy Fletcher

Permanent service only. OK PS, OH, RC, OK
ELE14-02974 Final10/24/201410/24/201410/24/2014 2:37:50 PMPFAIL
call prior to arrival for access. Phone #: ###-#### Inspection requested via web by Patrick Paz

408.4 Every circuit shall be identified as to its purpose
250.110 Equipment grounds loose in panel
ELE14-02974 Permanent Service10/24/201410/24/201410/24/2014 2:37:13 PMPPASS
call prior to arrival for access. Phone #: ###-#### Inspection requested via web by Patrick Paz

PS ,OH, RC OK

ELE14-02922 Electrical Rough-In10/22/201410/24/201410/24/2014 12:47:52 PMPPASS
trench insp // Bryant Phone #: ###-####

Trench OK
ELE14-02972 Final10/24/201410/24/201410/24/2014 12:34:45 PMPCANC
SPACE # 5 Phone #: ###-#### Inspection requested via web by Dan Rohl
ELE14-02972 Permanent Service10/24/201410/24/201410/24/2014 12:34:35 PMPFAIL
SPACE # 5 Phone #: ###-#### Inspection requested via web by Dan Rohl


4.05.32 Code violations not to be retained
250.53(a)(2) Supplemental electrode (ground rod) required 2 per service
314.23(A) Enclosures shall be rigidly and securly fastened in place
250.94(B)
Method of Bonding at the Service. Bonding jumpers
meeting the requirements of this article shall be used around
impaired connections, such as reducing washers or oversized,
concentric, or eccentric knockouts. Standard locknuts or bushings
shall not be the only means for the bonding required by
this section but shall be permitted to be installed to make a
mechanical connection of the raceway(s).
Electrical continuity at service equipment, service raceways,
and service conductor enclosures shall be ensured by
one of the following methods:
(1) Bonding equipment to the grounded service conductor
in a manner provided in 250.8
(2) Connections utilizing threaded couplings or threaded
hubs on enclosures if made up wrenchtight
(3) Threadless couplings and connectors if made up tight
for metal raceways and metal-clad cables
(4) Other listed devices, such as bonding-type locknuts,
bushings, or bushings with bonding jumpers
230.70 Marking. Each service disconnect shall be permanently
marked as to its purpose
ELE14-02971 Permanent Service10/24/201410/24/201410/24/2014 12:33:26 PMPFAIL
SPACE # 4 Phone #: ###-#### Inspection requested via web by Dan Rohl

4.05.32 Code violations not to be retained
250.53(a)(2) Supplemental electrode (ground rod) required 2 per service
314.23(A) Enclosures shall be rigidly and securly fastened in place
250.94(B)
Method of Bonding at the Service. Bonding jumpers
meeting the requirements of this article shall be used around
impaired connections, such as reducing washers or oversized,
concentric, or eccentric knockouts. Standard locknuts or bushings
shall not be the only means for the bonding required by
this section but shall be permitted to be installed to make a
mechanical connection of the raceway(s).
Electrical continuity at service equipment, service raceways,
and service conductor enclosures shall be ensured by
one of the following methods:
(1) Bonding equipment to the grounded service conductor
in a manner provided in 250.8
(2) Connections utilizing threaded couplings or threaded
hubs on enclosures if made up wrenchtight
(3) Threadless couplings and connectors if made up tight
for metal raceways and metal-clad cables
(4) Other listed devices, such as bonding-type locknuts,
bushings, or bushings with bonding jumpers
230.70 Marking. Each service disconnect shall be permanently
marked as to its purpose
ELE14-02970 Permanent Service10/24/201410/24/201410/24/2014 12:32:45 PMPFAIL
SPACE #1 Phone #: ###-#### Inspection requested via web by Dan Rohl
4.05.32 Code violations not to be retained
250.53(a)(2) Supplemental electrode (ground rod) required 2 per service
314.23(A) Enclosures shall be rigidly and securly fastened in place
250.94(B)
Method of Bonding at the Service. Bonding jumpers
meeting the requirements of this article shall be used around
impaired connections, such as reducing washers or oversized,
concentric, or eccentric knockouts. Standard locknuts or bushings
shall not be the only means for the bonding required by
this section but shall be permitted to be installed to make a
mechanical connection of the raceway(s).
Electrical continuity at service equipment, service raceways,
and service conductor enclosures shall be ensured by
one of the following methods:
(1) Bonding equipment to the grounded service conductor
in a manner provided in 250.8
(2) Connections utilizing threaded couplings or threaded
hubs on enclosures if made up wrenchtight
(3) Threadless couplings and connectors if made up tight
for metal raceways and metal-clad cables
(4) Other listed devices, such as bonding-type locknuts,
bushings, or bushings with bonding jumpers
230.70 Marking. Each service disconnect shall be permanently
marked as to its purpose
ELE14-02871 Final10/23/201410/24/201410/24/2014 11:10:40 AMPCANC
panel schedule and lock out done. Thanks Phone #: ###-#### Inspection requested via web by Rick Beckman
FInal OK
ELE14-02962 Final10/23/201410/24/201410/24/2014 10:27:58 AMAPASS
Final connections for coolers and freezers in front of store, and walk in cooler and walk in freezer in back of store. Phone #: ###-#### Inspection requested via web by Andy Rose

Freezers and coolers OK
ELE14-02870 Electrical Rough-In10/23/201410/24/201410/24/2014 9:59:57 AMAPASS
walls and ceilings for cover also look at service to see if ok like we did it call steve with questions Phone #: ###-#### Inspection requested via web by Don Lustig

Wall cover OK
ELE14-02960 Rough-In Permanent Service10/23/201410/24/201410/24/2014 9:10:26 AMAFAIL
Rough and Service inspection Inspection requested via web by Rowdy Monroe
300.13(B) Device Removal. In multiwire branch circuits, the
continuity of a grounded conductor shall not depend on
device connections such as lampholders, receptacles, and
so forth, where the removal of such devices would interrupt
the continuity.
ELE14-02965 Conference10/23/201410/24/201410/23/2014 12:00:00 AMADONE
Josh Phone #: ###-####-would like as early as possilbe and can you please call with a meet time?