Inspections for the day of: Friday, October 24, 2014.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD14-01596 FIRE-Final Inspection10/24/201410/24/201410/24/2014 3:33:53 PMPPART
Per discussion- Contractor to install missing exit signs, adjust doors and post occupancy sign today (10/24). Okayed tenant move based on these conditions. Contractor to request final inspection Monday 10/27 AM.
BLD14-02850 FIRE-Conference10/24/201410/24/201410/24/2014 3:22:33 PMPDONE
On site conference regarding FIR trade work, existing fire alarm coverage, life safety items.
BLD14-00613 FIRE-Final Inspection10/23/201410/24/201410/24/2014 3:15:13 PMPDONE
Inspection request intended for an on site conference regarding fire life safety conditions and requirements. Discussed door hardware, fire extinguishers, exit signs and EM lights, HVAC duct SD, premise identification, approved plan set, review notes, etc.
BLD14-01596 FIRE-Final Inspection10/23/201410/24/201410/24/2014 2:33:45 PMAFAIL
Items noted include; missing five exit signs per plan review red-lines, relocate one exit sign, provide directional arrow at one exit sign, fire doors at three locations need adjustment to full closure, post max occupancy signage at the large conference room.
FIR14-00605 INSP-Final Inspection10/23/201410/24/201410/24/2014 2:25:45 PMAPASS
Verified noted correction items, fire alarm work passed final inspection.
BLD14-02759 FIRE-Sprinkler Rough-in10/24/201410/24/201410/24/2014 10:34:44 AMAPART
Fire sprinkler work at the restroom sheetrock ceilings okay for cover.
FIR14-00565 INSP-Final Inspection10/23/201410/24/201410/24/2014 10:33:32 AMAPASS
Scope of fire sprinkler work completed. Permit final approved.
FIR14-00293 INSP-Final Inspection10/23/201410/24/201410/23/2014 2:35:34 PMAPASS
Okay for final status per C. Hanson.