BLD14-01596
| FIRE-Final Inspection | 10/24/2014 | 10/24/2014 | 10/24/2014 3:33:53 PM | P | PART |
|
|
Per discussion- Contractor to install missing exit signs, adjust doors and post occupancy sign today (10/24). Okayed tenant move based on these conditions. Contractor to request final inspection Monday 10/27 AM.
|
BLD14-02850
| FIRE-Conference | 10/24/2014 | 10/24/2014 | 10/24/2014 3:22:33 PM | P | DONE |
|
|
On site conference regarding FIR trade work, existing fire alarm coverage, life safety items.
|
BLD14-00613
| FIRE-Final Inspection | 10/23/2014 | 10/24/2014 | 10/24/2014 3:15:13 PM | P | DONE |
|
|
Inspection request intended for an on site conference regarding fire life safety conditions and requirements. Discussed door hardware, fire extinguishers, exit signs and EM lights, HVAC duct SD, premise identification, approved plan set, review notes, etc.
|
BLD14-01596
| FIRE-Final Inspection | 10/23/2014 | 10/24/2014 | 10/24/2014 2:33:45 PM | A | FAIL |
|
|
Items noted include; missing five exit signs per plan review red-lines, relocate one exit sign, provide directional arrow at one exit sign, fire doors at three locations need adjustment to full closure, post max occupancy signage at the large conference room.
|
FIR14-00605
| INSP-Final Inspection | 10/23/2014 | 10/24/2014 | 10/24/2014 2:25:45 PM | A | PASS |
|
|
Verified noted correction items, fire alarm work passed final inspection.
|
BLD14-02759
| FIRE-Sprinkler Rough-in | 10/24/2014 | 10/24/2014 | 10/24/2014 10:34:44 AM | A | PART |
|
|
Fire sprinkler work at the restroom sheetrock ceilings okay for cover.
|
FIR14-00565
| INSP-Final Inspection | 10/23/2014 | 10/24/2014 | 10/24/2014 10:33:32 AM | A | PASS |
|
|
Scope of fire sprinkler work completed. Permit final approved.
|
FIR14-00293
| INSP-Final Inspection | 10/23/2014 | 10/24/2014 | 10/23/2014 2:35:34 PM | A | PASS |
|
|
Okay for final status per C. Hanson.
|