Inspections for the day of: Monday, October 24, 2016.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-03416 Electrical Rough-In10/20/201610/24/201610/25/2016 8:59:21 AMAPASS
Phone #: ###-#### Inspection requested via web by Barbara Szurgot
Checked all electrical as garage was energized. Unable to final due to all wiring exposed below 8' shall be protected from physical damage by wall cover or guard strips.
Garage rough in ok cover
ELE16-01838 Electrical Rough-In10/22/201610/24/201610/24/2016 2:11:26 PMPPASS
level 1 stack 1 ceiling. call Brandon Phone #: ###-#### Inspection requested via web by Brandon Robinson
Customer experience N. E corner and S. E. corner 5 rooms hardlids rough in ok cover
ELE16-03440 Rough-In Permanent Service10/24/201610/24/201610/24/2016 1:31:41 PMPPASS
Please call so I can get you in Phone #: ###-#### Inspection requested via web by Eddy Udry
Rough in of permanent service only. This permit to cover trim portion of job. Contractor to cover any issue from here to completion. ELE16-00937 is permit that covers rough in portion of job. West garage has wall cover on PVC LB fittings on outside of structure, contractor to make access to LB.

p/s u/g n ok
ELE16-03413 Electrical Rough-In10/21/201610/24/201610/24/2016 10:35:18 AMAFAIL
Will call Monday to fix application price on permit. Phone #: ###-#### Inspection requested via web by Charles Davis
110.3- Service riser shall be installed as per manufacterers instructions. Shall provide for rise and fall of conduit.
110.12(B)- Service riser coupling broken.
300.4- Nail plates shall protect NM cable where hole does not maintain 1 1/4" from framing surface. 45 degree corners and others.
300.15- Can over vanity secure cover on junction box.
334.12- NM cable shall not be installed where subject to physical damage. Hangs below truss in garage.
ELE16-00751 Final10/21/201610/24/201610/24/2016 9:25:37 AMAPART
units 205 209 117 123 124 129 Phone #: ###-#### Inspection requested via web by Tracy Robertson
Rooms noted only exterior not complete.
ELE16-00752 Final10/21/201610/24/201610/24/2016 9:24:49 AMAPART
units 328 225 Phone #: ###-#### Inspection requested via web by Tracy Robertson
Rooms noted only, exterior not complete.