Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-01908 FIRE-Final Inspection10/24/201610/24/201610/24/2016 2:38:35 PMPPASS
No need for fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
BLD16-03796 FIRE-Final Inspection10/21/201610/24/201610/24/2016 1:31:06 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags, inspection tag is current for fire sprinklers (Annual inspection due DEC2016) Appears to have no upgrades to door hardware, noted that southside exterior door has round type door hardware, final life fire safety inspection passed/complete.
FIR16-00480 INSP-Sprinkler Rough-in10/21/201610/24/201610/24/2016 11:47:55 AMACANC
This FIR permit is for underground supply, inspection request is for rough in inspection for overhead fire sprinkler piping (FIR16-00534). This inspection request is cancelled and the correct permit has been shceduled.
FIR16-00534 INSP-Sprinkler Rough-in10/24/201610/24/201610/24/2016 11:46:02 AMAPART
Rough in inspection for overhead fire sprinkler piping complete, another rough to cover inspection will need to be performed for cover after ceiling grid and finish pendant heads are installed.
FIR16-00615 INSP-Sprinkler Rough-in10/21/201610/24/201610/24/2016 8:50:01 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping complete for area of work, overhead fire sprinkler piping in area of work approved for cover.
BLD14-02173 FIRE-Final Inspection10/21/201610/24/201610/24/2016 7:12:36 AMAPART
Generator transfer for interior emergency/egress lighting tested/inspected for levels 1 through 9, exit signs on level 6 south balcony did not operate under emergency power, will verify operation on a future inspection. Exterior emergency egress lighting and parking level emergency egress/exit lighting will also be verified during a future inspection.
BLD16-03125 FIRE-Final Inspection10/21/201610/24/201610/24/2016 7:06:43 AMACANC
Final life fire safety inspection completed on 21OCT2016