Inspections for the day of: Tuesday, October 24, 2017.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC17-04566 Final10/23/201710/24/201710/24/2017 4:13:25 PMPPASS
Homeowner will be home after 2:30PM. Please do inspection no earlier than 2:30PM, Thanks. Phone #: ###-#### Inspection requested via web by Kim Lithander- Furnace ok- CO detectors installed
MEC17-04651 Final10/24/201710/24/201710/24/2017 3:45:58 PMPPASS
Phone #: ###-#### Inspection requested via web by Ron Arnold- furnace ok- CO installed
MEC17-04651 Pressure Test10/24/201710/24/201710/24/2017 3:45:25 PMPCANC
Phone #: ###-#### Inspection requested via web by Ron Arnold- not needed to witness unconditioned space thru attic
MEC17-01056 Final10/23/201710/24/201710/24/2017 3:04:51 PMPPART
HOMEOWNER WAS IN HOSPITAL FOR FEW MONTHS AND JUST NOW STARTING TO GET THINGS CAUGHT UP AND ON TRACK, SHE APOLOGIZES ABOUT THE DELAY ON THIS FINAL INSPECTION BUT WANTS TO STILL GET THIS COMPLETED. SET FOR PM INSPECTION AND PLEASE CALL HOMEOWNER WHEN 30 MINS IN ROUTE- HER NAME IS ANN JONES- ###-#### Phone #: ###-#### Inspection requested via web by Rick Montgomery- need right size fuses in disconnect for A/C has 20 needs 15 max
MEC17-04735 Final10/23/201710/24/201710/24/2017 2:35:24 PMPPASS
installer Brian ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt
MEC17-04712 Rough-in10/24/201710/24/201710/24/2017 2:06:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Jasmin Godina
MEC17-04741 Rough-in10/24/201710/24/201710/24/2017 1:45:46 PMPCANC
Will Phone #: ###-####- should have been conference- talked about issues on correction notice- need to resubmit manual J for new duct routing as installed
MEC17-04741 Pressure Test10/23/201710/24/201710/24/2017 1:40:51 PMAPART
Will Phone #: ###-####- 60lb gas pass- 20lb gas pass inside house- need to pressure test outdoor underground to firepit
MEC17-04741 Pressure Test10/24/201710/24/201710/24/2017 1:38:55 PMPCANC
Will Phone #: ###-####- should have been conference
MEC17-04720 Final10/24/201710/24/201710/24/2017 12:24:37 PMPPASS
Phone #: ###-#### Inspection requested via web by Krista Boss
MEC17-04741 Rough-in10/23/201710/24/201710/24/2017 11:18:16 AMANR
Will Phone #: ###-####- R/I incomplete- 6" fresh air can not come from roof- crawl incomplete- duct 2nd floor R/A not ran like manual J shows- need to insulate bare supply metal in attic- linesets need ran to both units- gas regulator locations?/- 18 to 16 reducer needs installed in shaft- dryer vent to long need to address- left correction notice front entry window
MEC17-04742 Pressure Test10/23/201710/24/201710/24/2017 10:34:41 AMAPASS
Phone #: ###-#### Inspection requested via web by Don Headrick- 20lb gas pass underground from meter to firepit-
MEC17-04542 Rough-in10/23/201710/24/201710/24/2017 9:37:15 AMAPASS
mechanical fireplace rough in inspection Phone #: ###-#### Inspection requested via web by Dan Otero- FP R/I ok
MEC17-04632 Rough-in10/23/201710/24/201710/24/2017 9:36:41 AMAPASS
Re-inspection of the Rough In. Phone #: ###-#### Inspection requested via web by Frank Marturello- correction made
MEC17-04384 Final10/23/201710/24/201710/24/2017 8:55:37 AMAPASS
FINAL INSPECTION FOR CARRIER 2.5 TON A/C ; 80% FURNACE INSTALL. PLEASE CALL (HOMEOWNER) CAROL @ # LISTED WHEN EN ROUTE. Phone #: ###-#### Inspection requested via web by SOPHIA FLEMING- furnace A/C ok- CO detectors installed