FIR17-00617
| INSP-Sprinkler Rough-in | 10/23/2017 | 10/24/2017 | 10/24/2017 1:28:57 PM | P | PART |
|
|
Cover inspection for partial underground passed. See the city approved plans for location of piping that is ok for cover. Today was for riser to the tee.
|
FIR17-00360
| INSP-Final Inspection | 10/20/2017 | 10/24/2017 | 10/24/2017 1:07:42 PM | P | FAIL |
|
|
Today I was only able to verify strobe placement. See the city approved plans for locations where strobes are overspaced, too high or needing to be added. As-built needed prior to a final sign off. Small documents are missing. Data sheets are missing. No sprinkler interconnections have been pre-tested.
|
FIR17-00146
| INSP-Final Inspection | 10/20/2017 | 10/24/2017 | 10/24/2017 1:05:29 PM | P | FAIL |
|
|
Not ready for final inspection yet due to fire alarm contractor not ready. Need forward flush, need signage and calc stickers....ect
|
FIR17-00107
| INSP-Final Inspection | 10/20/2017 | 10/24/2017 | 10/24/2017 1:04:12 PM | P | PASS |
|
|
Permit finaled
|
BLD16-04253
| FIRE-Final Inspection | 10/24/2017 | 10/24/2017 | 10/24/2017 12:02:55 PM | P | CANC |
|
|
Phone #: ###-#### >> Inspection requested via web by Darius Saxton Inspection cancelled from web by: Darius Saxton
|
FIR17-00303
| INSP-Sprinkler Rough-in/Hydro | 10/23/2017 | 10/24/2017 | 10/24/2017 10:22:28 AM | A | PASS |
|
|
Underground supply line hydro passed. I also did a partial rough-in on just the overhead pipe, hangers and seismic bracing. Minor corrections are needed. No piping can be covered until corrections and all drops are installed and inspected.
|
FIR17-00305
| INSP-Sprinkler Rough-in/Hydro | 10/23/2017 | 10/24/2017 | 10/24/2017 10:21:49 AM | A | PASS |
|
|
Underground supply line hydro passed. I also did a partial rough-in on just the overhead pipe, hangers and seismic bracing. Minor corrections are needed. Per Todd resubmittals are in the works. No piping can be covered until corrections, plan mods and all drops are installed and inspected.
Todd Ketterling Phone #: ###-####
|
FIR16-00284
| INSP-Final Inspection | 10/24/2017 | 10/24/2017 | 10/24/2017 10:08:13 AM | P | CANC |
|
|
Before 2:00 am or after 3:00 call ahead the elevator guy can’t be here between 2:00 and 3:00. Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
|
BLD17-02743
| FIRE-Final Inspection | 10/23/2017 | 10/24/2017 | 10/24/2017 7:47:45 AM | A | PASS |
|
|
life safety passed
|
BLD17-02697
| FIRE-Final Inspection | 10/23/2017 | 10/24/2017 | 10/24/2017 7:46:30 AM | A | PASS |
|
|
Life safety passed
John Phone #: ###-####
|
FIR17-00570
| INSP-Final Inspection | 10/23/2017 | 10/24/2017 | 10/24/2017 7:45:39 AM | A | PASS |
|
|
Permit finaled
|