Inspections for the day of: Tuesday, October 24, 2017.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00617 INSP-Sprinkler Rough-in10/23/201710/24/201710/24/2017 1:28:57 PMPPART
Cover inspection for partial underground passed. See the city approved plans for location of piping that is ok for cover. Today was for riser to the tee.
FIR17-00360 INSP-Final Inspection10/20/201710/24/201710/24/2017 1:07:42 PMPFAIL
Today I was only able to verify strobe placement. See the city approved plans for locations where strobes are overspaced, too high or needing to be added. As-built needed prior to a final sign off. Small documents are missing. Data sheets are missing. No sprinkler interconnections have been pre-tested.
FIR17-00146 INSP-Final Inspection10/20/201710/24/201710/24/2017 1:05:29 PMPFAIL
Not ready for final inspection yet due to fire alarm contractor not ready. Need forward flush, need signage and calc stickers....ect
FIR17-00107 INSP-Final Inspection10/20/201710/24/201710/24/2017 1:04:12 PMPPASS
Permit finaled
BLD16-04253 FIRE-Final Inspection10/24/201710/24/201710/24/2017 12:02:55 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Darius Saxton Inspection cancelled from web by: Darius Saxton
FIR17-00303 INSP-Sprinkler Rough-in/Hydro10/23/201710/24/201710/24/2017 10:22:28 AMAPASS
Underground supply line hydro passed. I also did a partial rough-in on just the overhead pipe, hangers and seismic bracing. Minor corrections are needed. No piping can be covered until corrections and all drops are installed and inspected.
FIR17-00305 INSP-Sprinkler Rough-in/Hydro10/23/201710/24/201710/24/2017 10:21:49 AMAPASS
Underground supply line hydro passed. I also did a partial rough-in on just the overhead pipe, hangers and seismic bracing. Minor corrections are needed. Per Todd resubmittals are in the works. No piping can be covered until corrections, plan mods and all drops are installed and inspected.

Todd Ketterling Phone #: ###-####
FIR16-00284 INSP-Final Inspection10/24/201710/24/201710/24/2017 10:08:13 AMPCANC
Before 2:00 am or after 3:00 call ahead the elevator guy can’t be here between 2:00 and 3:00. Phone #: ###-#### >> Inspection requested via web by Sam Ball Inspection cancelled from web by: Sam Ball
BLD17-02743 FIRE-Final Inspection10/23/201710/24/201710/24/2017 7:47:45 AMAPASS
life safety passed
BLD17-02697 FIRE-Final Inspection10/23/201710/24/201710/24/2017 7:46:30 AMAPASS
Life safety passed

John Phone #: ###-####
FIR17-00570 INSP-Final Inspection10/23/201710/24/201710/24/2017 7:45:39 AMAPASS
Permit finaled