Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02862 Electrical Rough-In10/24/201810/24/201810/24/2018 2:24:36 PMPPASS
Underground conduit for street pole lighting Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Informed to be sure to call public works about street light installation.
Idaho street west pole base and underground rough in ok cover.
ELE18-04108 Electrical Rough-In10/24/201810/24/201810/24/2018 1:55:20 PMPPASS
Ground inspection for island and floor outlets Phone #: ###-#### Inspection requested via web by Zane Robertson
Underground Rough in ok cover
ELE18-02352 Final10/24/201810/24/201810/24/2018 1:16:24 PMPPASS
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
ELE18-04077 Temporary Service10/23/201810/24/201810/24/2018 12:12:48 PMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
ELE18-02581 Final10/23/201810/24/201810/24/2018 11:58:22 AMANR
Garage code is 7352 enter Phone #: ###-#### Inspection requested via web by Zane Robertson
House tested ok, small water feature being installed in back yard at time of inspection that shall be tested
ELE18-04092 Final10/23/201810/24/201810/24/2018 11:17:03 AMAPASS
Phone #: ###-#### Inspection requested via web by steve ragan Final ok
ELE18-04098 Rough-In Permanent Service10/24/201810/24/201810/24/2018 10:36:17 AMAFAIL
Phone #: ###-#### Inspection requested via web by Therrin Robertson
110.12(A)- Unused openings shall be closed by approved means. 2" KO in bottom of meterbase.
300.4- Nail plates needed where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface. Garage.
314.25- Recessed can junction box cover shall be installed so it totally cover opening in box. near bottom of stair back cover partailly off.
352.46- Where UF cable enters or emerges from PVC conduit it shall be protected from damage by bushings.
408.7- Unused breaker openings shall be closed by aproved means.
ELE18-04099 Rough-In Permanent Service10/24/201810/24/201810/24/2018 10:26:34 AMAFAIL
Phone #: ###-#### Inspection requested via web by Therrin Robertson
225.31- A disconnecting means shall be provided for seperate garage structure on exterior or where conductors enter structure.
300.4- Nail plates shall be installed where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface.
300.4(B)(1)- NM cables shall be protected from damage where they enter an enclosure. Connectors shall be installed as per manufacturers instructions. Connectors not completely installed at front outdoor receptacle box, both junction boxes for garage wiring at house nad garage, service.
314.25- Recessed can junction box shall be installed to totally cover opening in box. Can at top of stair back cover partially off.
352.46- Where UF cable enters or emerges from PVC conduit it shall be protected from damage by a bushing.
408.7- Unused breaker openings shall be closed.
ELE18-03320 Electrical Rough-In10/23/201810/24/201810/24/2018 9:03:25 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Level 5 hardlids rough in ok cover