Inspections for the day of: Friday, October 25, 2002.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE01-01532 Final10/22/200210/25/200210/25/2002 12:00:00 AMACANC
had a partial fn insp??postcard- cori- ###-#### call 1st before insp
ELE02-03318 Permanent Service10/24/200210/25/200210/25/2002 12:00:00 AMAPART
###-#### ready at 10:30
P/S O/H R Ok
check access to water bond and dryer ckt 10/25/2002 11:07:49 AM
ELE02-03308 Electrical Rough-In10/24/200210/25/200210/25/2002 12:00:00 AMAPASS
###-####
ELE02-03169 Rough-In Permanent Service10/24/200210/25/200210/25/2002 12:00:00 AMAFAIL
Scheduled by a contractor via Hello! on 10/24/2002 at 11:43:47. Contact: ###-####.Undersized GEC to 200a disconnect 10/25/2002 9:41:19 AM
ELE02-03277 Temporary Service10/24/200210/25/200210/25/2002 12:00:00 AMAFAIL
GORDEN ###-####
correction not made 10/25/2002 8:57:13 AM
ELE02-02758 Electrical Rough-In10/24/200210/25/200210/25/2002 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 10/24/2002 at 13:36:34. Contact: ###-####.
Ok to cover ceiling except where makeup is required. 10/25/2002 10:10:45 AM
ELE02-03105 Electrical Rough-In10/25/200210/25/200210/25/2002 12:00:00 AMPPART
###-#### Jackie (cover)
U/G and office walls ok 10/25/2002 3:15:01 PM
ELE02-03335 Temporary Service10/25/200210/25/200210/25/2002 12:00:00 AMPFAIL
chris ###-####
110.12 Mechanical Execution of Work.
(C) Integrity of Electrical Equipment and Connections. Internal parts of electrical equipment, ……. shall not be damaged or contaminated

250.92 Services.
(A) Bonding of Services. The non-current-carrying metal parts of equipment indicated in 250.92(A)(1), (2), and (3) shall be effectively bonded together.

250.53 Grounding Electrode System Installation.
G) Rod and Pipe Electrodes.
where rock bottom is encountered, the electrode shall be driven at an oblique angle not to exceed 45 degrees from the vertical
10/25/2002 1:16:11 PM
ELE01-01532 Final10/25/200210/25/200210/25/2002 12:00:00 AMPPASS
ELE02-03277 Temporary Service10/25/200210/25/200210/25/2002 12:00:00 AMPPASS
###-####
T/S U/G Ok 10/25/2002 2:19:45 PM
ELE02-02982 Electrical Rough-In10/25/200210/25/200210/25/2002 12:00:00 AMPPASS
upher ground ###-####