BLD04-01729 FIRE-Conference10/25/200410/25/200410/25/2004 12:00:00 AMADONE
I found backboxes and conduit installed on this project for the fire alarm system. I posted a stop work order for the installation of the fire alarm system and the installation of sheet rock (which will cover the conduit and backboxes). I don't know at this time who started to install the fire alarm system.
MIS04-00292 FIR-Final10/25/200410/25/200410/25/2004 12:00:00 AMPPART
A temporary occupancy was given until items on the correction notice have been addressed. These items include overspaced pendants, missing canopies, column blockage and uprights at draftstops are overspaced. Rear doors are bolted and locked shut. Exit sign and emergency light missing at the southeast exit. Other exit signs and emergency lights have not been tested. Not all fire extinguishers have been installed. Door hardware needs to be re-installed on the northwest exit. Owner needs to hire a fire sprinkler contractor to correctly access all deficiencies. There is also a valve on an anti-freeze loop that is not electronically monitored. This will be turned over to the fire dept for further action. 10/25/2004 2:41:21 PM
BLD03-02533 FIRE-Final Inspection10/25/200410/25/200410/25/2004 12:00:00 AMPPASS
Fire life safety finaled 10/25/2004 4:24:58 PM
FIR04-00623 INSP-Sprinkler Rough-in/Hydro10/25/200410/25/200410/25/2004 12:00:00 AMPPART
Sprinkler rough-in for piping in canopy is ok. Plan resubmittals need to be submitted and approved before any other inspections are called in. 10/25/2004 3:04:55 PM
FIR03-00586 INSP-Final Inspection10/25/200410/25/200410/25/2004 12:00:00 AMPFAIL
Inspection was stopped due to so many items being incorrect. Phone lines are not being supervised. Smoke detector installed is not the one submitted. Supervisory signal latches. No map of initiating devices. Need zone description at annunciator. No one to test the new tamper switches. Strobe does not work.