Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03886 Electrical Rough-In10/25/200510/25/200510/25/2005 4:31:58 PMPPASS
Ufer inspection. Ufer is straight away from pole in foundation.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs ok to cover gec, left sticker on gec.
ELE05-03106 Final10/25/200510/25/200510/25/2005 4:20:14 PMPPASS
WARREN; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to final
ELE05-01293 Permanent Service10/25/200510/25/200510/25/2005 3:08:08 PMPPASS
any questions please give Ed Schallock a call; Phone #: ###-#### Internet Inspection Request from: Jeff Radford p/s u/g n ok
ELE05-02837 Final10/25/200510/25/200510/25/2005 2:34:10 PMPFAIL
tim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 410.8 closet light shall be 12" from storage area
ELE05-03883 Temporary Service10/25/200510/25/200510/25/2005 1:52:01 PMPPASS
Temp pole is on east side by transformer.; Phone #: ###-#### Internet Inspection Request from: Kathy Briggs t/s u/g n ok
ELE05-03885 Temporary Service10/25/200510/25/200510/25/2005 1:01:42 PMPFAIL
###-#### - spencer called contr,left corr notice, fee due, BCC job id shall be posted, 312.5 gec shall have abrasion protection, 250.64(B) gec shall be securely fastened
ELE05-03867 Electrical Rough-In10/25/200510/25/200510/25/2005 12:21:19 PMPPASS
chris; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections made, ric ok, p/s u/g n ok
ELE05-03874 Electrical Rough-In10/24/200510/25/200510/25/2005 10:39:51 AMAPASS
###-#### - ron ric ok, p/s u/g n ok
ELE05-03875 Permanent Service10/24/200510/25/200510/25/2005 9:56:24 AMACANC
chuck ###-#### talked to contr, told to amend permit and call for service change and also p/s inspection.A new service has been installed inside tlr.
ELE05-03241 Rough-In Permanent Service10/24/200510/25/200510/25/2005 9:54:28 AMAPASS
Scheduled by a contractor via Hello! on 10/24/2005 at 12:49:16 PM. Contact: ###-####. looked at service after incident ,called IPCO, p/s ok n exst meter pak