FIR05-00538
| FIR-Aging Inspection | 10/25/2006 | 10/25/2006 | 10/31/2006 12:07:13 PM | | DEFR |
|
|
|
FIR06-00423
| INSP-Final Inspection | 10/24/2006 | 10/25/2006 | 10/25/2006 5:37:30 PM | A | PART |
|
|
Rough-in is acceptable for cover at the drop ceilings.
|
FIR06-00424
| INSP-Final Inspection | 10/24/2006 | 10/25/2006 | 10/25/2006 5:36:56 PM | A | PART |
|
|
OH rough-in is good for cover at the drop ceiling areas.
|
FIR06-00422
| INSP-Final Inspection | 10/24/2006 | 10/25/2006 | 10/25/2006 5:36:14 PM | A | PART |
|
|
Okay to cover OH rough-in at the drop ceiling areas.
|
BLD05-03415
| FIRE-Final Inspection | 10/20/2006 | 10/25/2006 | 10/25/2006 5:35:26 PM | A | CANC |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles Inspection to be rescheduled per conversation with contractor as project is not ready for final at this time.
|
FIR06-00502
| INSP-Alarm Testing | 10/24/2006 | 10/25/2006 | 10/25/2006 5:34:13 PM | P | FAIL |
|
|
The PIV tamper switch is not adjusted accurately, supervisory tamper switches shall be non-latching per requirements, need to provide a sign at the door to the room containing the FACP per review note #16.
|
FIR06-00126
| INSP-Final Inspection | 10/24/2006 | 10/25/2006 | 10/25/2006 5:30:14 PM | P | PASS |
|
|
UG fire supply line permit finaled.
|
BLD06-01860
| FIRE-Final Inspection | 10/24/2006 | 10/25/2006 | 10/25/2006 10:07:20 AM | A | PASS |
|
|
Required corrections have been made, fire life safety finaled.
|