FIR07-00694
| INSP-Conference | 10/19/2007 | 10/22/2007 | | A | |
|
|
PIV issue
|
FIR07-00525
| INSP-Final Inspection | 10/23/2007 | 10/25/2007 | 10/26/2007 4:24:05 PM | P | FAIL |
|
|
See approved plans 1st floor for areas in need of repair including three SD to be relocated, strobes are not in sync at the pool room, fireman's hat needs to illuminate solid upon activation of the SD at the elevator lobby, need to test EOL, provide signals report at next inspection, noted corrections have been verified from the previous inspection.
|
FIR06-00007
| INSP-Final Inspection | 10/23/2007 | 10/25/2007 | 10/25/2007 5:21:22 PM | A | DEFR |
|
|
Scheduled for 10/26
|
FIR07-00305
| INSP-Final Inspection | 10/24/2007 | 10/25/2007 | 10/25/2007 3:08:33 PM | A | NR |
|
|
Project is not in condition for final approval, also need to coordinate inspection with the sprinkler contractor, discussed project schedule.
|
FIR07-00441
| INSP-Final Inspection | 10/25/2007 | 10/25/2007 | 10/25/2007 2:19:45 PM | P | NH |
|
|
No access available to the areas in need of inspection.
|
BLD06-02598
| FIRE-Final Inspection | 10/24/2007 | 10/25/2007 | 10/25/2007 2:17:53 PM | P | FAIL |
|
|
Provide building address numbers, remove the manual thumbturn at the door from the SW office, provide signage at the door the to fire riser room.
|
FIR07-00716
| INSP-Final Inspection | 10/25/2007 | 10/25/2007 | 10/25/2007 12:15:43 PM | P | FAIL |
|
|
Still missing field ceiling tiles at several locations.
|
FIR07-00812
| INSP-Sprinkler Rough-in | 10/24/2007 | 10/25/2007 | 10/25/2007 11:44:35 AM | A | PART |
|
|
UG fire supply line installation per scope of work is acceptable pending satisfactory compliance with Boise City Fire Prevention Code adoption 7-01-46. The fire service line must be dedicated single use for the overhead fire sprinkler system or be looped if accomodating both hydrants and OH supply. Notified contractor of the situation. Per Jim Danes of American Fire the line is planned for future looped connection, date uncertain. Per the civil drawings, the UG fire service line is shown as single use for OH fire protection only.
|
FIR07-00360
| FIR-Aging Inspection | 10/25/2007 | 10/25/2007 | 10/25/2007 11:30:55 AM | | DEFR |
|
|
Work in progress.
|
FIR07-00364
| INSP-Final Inspection | 10/25/2007 | 10/25/2007 | 10/25/2007 11:01:36 AM | P | PASS |
|
|
UG fire supply line permit finaled.
|
FIR06-00562
| INSP-Final Inspection | 10/24/2007 | 10/25/2007 | 10/25/2007 10:34:26 AM | A | PASS |
|
|
Final inspection passed per K. Roule, fire alarm permit finaled.
|
BLD07-01744
| FIRE-Final Inspection | 10/24/2007 | 10/25/2007 | 10/25/2007 10:31:40 AM | A | NR |
|
|
EM lights and exit signs are not ready.
|
FIR07-00765
| INSP-Final Inspection | 10/24/2007 | 10/25/2007 | 10/25/2007 10:29:51 AM | A | PASS |
|
|
Fire sprinkler passed final inspection, permit finaled.
|