Inspections for the day of: Thursday, October 25, 2007.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00671 INSP-Final Inspection10/25/200710/25/200710/26/2007 4:06:05 PMPFAIL
mike timmerman is working through the inspection. There appear to be deficiencies with the existing devices such as being placed too close to supply diffusers.
FIR07-00811 INSP-Sprinkler Rough-in10/25/200710/25/200710/26/2007 4:03:28 PMPCANC
overbooked due to micron plan review
BLD06-03515 FIRE-Final Inspection10/23/200710/25/200710/26/2007 4:01:47 PMPFAIL
The smoke control system is not working correctly as per Mike Timmerman.
FIR07-00380 INSP-Alarm Testing10/23/200710/25/200710/26/2007 12:34:37 PMAFAIL
Need the smoke control system approved and the strobes to cease when the silence button is activated.
FIR07-00766 INSP-Sprinkler Rough-in10/25/200710/25/200710/26/2007 7:35:05 AMPCANC
Overbooked with micron
FIR07-00380 INSP-Alarm Testing10/22/200710/25/200710/25/2007 12:54:34 PMACANC
Duplicate inspection for today.
FIR07-00769 INSP-Final Inspection10/24/200710/25/200710/25/2007 12:53:56 PMAFAIL
The electrician did not correctly re-install the wiring in the butterfly control valve. Has been rescheduled for tomorrow.
FIR07-00726 INSP-Sprinkler Rough-in/Hydro10/24/200710/25/200710/25/2007 12:39:30 PMPFAIL
Inspection was scheduled for afternoon but due to Micron I tried to do it this morning. I found the guage below 200 psi and the fdc and the riser/header not part of the test.
FIR07-00336 INSP-Sprinkler Rough-in/Hydro10/24/200710/25/200710/25/2007 12:38:34 PMPFAIL
Inspection was scheduled for afternoon but due to Micron I tried to do it this morning. I found the guage below 200 psi and the fdc and the riser/header not part of the test.
BLD07-01915 FIRE-Final Inspection10/24/200710/25/200710/25/2007 12:33:06 PMAPASS
life safety passed
BLD07-02720 FIRE-Final Inspection10/24/200710/25/200710/25/2007 11:09:52 AMAFAIL
Provide sticker at the main exit, provide automatic flush bolts at the main exit, provide fire extinguisher in the new storage area, provide revised sprinkler coverage in the existing storage area and comply with note #9 for the installation of the new insulation.
FIR07-00629 FIR-Aging Inspection10/25/200710/25/200710/25/2007 9:48:25 AM NR
work is in progress
FIR07-00732 INSP-Final Inspection10/24/200710/25/200710/25/2007 9:47:12 AMAPASS
Permit finaled
BLD07-02537 FIRE-Final Inspection10/24/200710/25/200710/25/2007 8:57:55 AMAPASS
Life safety passed.