Inspections for the day of: Friday, October 25, 2013.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02286 Final10/25/201310/25/201310/25/2013 4:09:08 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Darryn Coburn Final ok
ELE13-02930 Permanent Service10/25/201310/25/201310/25/2013 3:41:38 PMPFAIL
Abel Phone #: ###-#### 230.41- Service entrance conductors shall be insulated.
250.24- Grounding electode conductors shall terminate at same terminal or bus bar as grounded conductor.
250.64- Metal piping system shall be bonded, cold first then hot.
250.80- Equiptment bonding strap shall be installed.
Annex C Table C1- Max # of conductors in EMT 3 THW condutors from disconnect to sub panel.
ELE13-02558 Electrical Rough-In10/25/201310/25/201310/25/2013 3:19:50 PMPPASS
Danny. Wall Cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy office wall rough in complete ok cover
ELE13-02989 Electrical Rough-In10/25/201310/25/201310/25/2013 1:44:35 PMPPASS
Wiring for hood with outlets both sides cut in to the existing wall (no new walls on this one) Phone #: ###-#### >> Inspection requested via web by Brad Baker Power additions east wall rough in ok cover
ELE13-02448 Electrical Rough-In10/25/201310/25/201310/25/2013 1:43:23 PMPCANC
Phone #: ###-#### >> Inspection requested via web by Kerri Hamilton Inspection cancelled from web by: Kerri Hamilton
ELE13-02922 Conference10/18/201310/25/201310/25/2013 1:27:23 PMPDONE
Please call 1hr prior - Frank Phone #: ###-#### Discussed remodel of kitchen ceiling, mudroom, and bed wall moved.
GCE13-00113 GCE-Permanent Service10/25/201310/25/201310/25/2013 12:30:00 PMPPASS
Mike ###-#### This is for final. Call l/2 hour prior. Final ok
ELE13-02980 Final10/25/201310/25/201310/25/2013 10:15:12 AMAPASS
contact engineering dept. for location Phone #: ###-#### >> Inspection requested via web by PAT MILLER Final ok
ELE13-02980 Electrical Rough-In10/25/201310/25/201310/25/2013 10:07:37 AMAPASS
contact engineering dept. for location Phone #: ###-#### >> Inspection requested via web by PAT MILLER Outlet addition rough in ok
ELE13-02974 Electrical Rough-In10/25/201310/25/201310/25/2013 9:44:13 AMAPASS
Phone #: ###-#### >> Inspection requested via web by John VanZandt Garage, mudroom, closet and bedroom addition rough in ok cover
ELE13-01715 Final10/24/201310/25/201310/25/2013 9:28:05 AMAPASS
Code is 1905 Phone #: ###-#### >> Inspection requested via web by kevin blackmon
Final ok
GCE13-00176 GCE-Permanent Service10/24/201310/25/201310/25/2013 8:51:57 AMACANC
David ###-#### Needed temp service
GCE13-00176 GCE-Temporary Service10/25/201310/25/201310/25/2013 8:51:34 AMPPASS
David ###-#### t/s u/g n ok