Inspections for the day of: Friday, October 25, 2013.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00798 INSP-Final Inspection10/24/201310/25/201310/29/2013 3:36:59 PMADEFR
Inspection scheduled 10/31
BLD13-02984 FIRE-Final Inspection10/24/201310/25/201310/25/2013 10:04:26 PMPPASS
Fire life safety finaled.
BLD13-01966 FIRE-Final Inspection10/24/201310/25/201310/25/2013 10:02:48 PMPPASS
Life safety finaled.
BLD13-02869 FIRE-Final Inspection10/25/201310/25/201310/25/2013 3:11:50 PMPPART
Final pending missing fire extinguisher, cover one open junction box at the ceiling.
FIR13-00453 INSP-Final Inspection10/25/201310/25/201310/25/2013 3:08:56 PMPPASS
UG fire supply line permit okayed for final.
FIR13-00555 INSP-Sprinkler Rough-in10/24/201310/25/201310/25/2013 3:07:33 PMAPART
Overhead work at the sheetrock ceilings in the employee restroom and soffits at the private dining rooms as marked and dated on approved plans okayed for cover.
FIR13-00264 INSP-Sprinkler Rough-in10/25/201310/25/201310/25/2013 2:06:02 PMPPART
24 hr. air test of the new dry system completed with no pressure loss at the guage.
BLD13-01509 FIRE-Final Inspection10/24/201310/25/201310/25/2013 11:07:11 AMAPART
Fire life safety final pending a current annual inspection for the existing overhead fire sprinkler system. Last recorded certification tag on the riser dated 2010.
FIR13-00425 INSP-Final Inspection10/23/201310/25/201310/25/2013 11:05:09 AMAPASS
Fire sprinkler work passed final inspection.
FIR13-00453 INSP-Supply line flush10/24/201310/25/201310/25/2013 10:30:53 AMAPART
UG fire supply line flush completed satisfactory.
FIR13-00445 INSP-Final Inspection10/24/201310/25/201310/25/2013 9:58:53 AMAPASS
Inspection passed. Fire sprinkler permit work finaled.
FIR13-00444 INSP-Final Inspection10/24/201310/25/201310/25/2013 9:57:55 AMAPASS
Fire sprinkler permit finaled.